 ** DENIEDREVIEW **
  
 1) NOTE: PLEASE SEE THE FOLLOWING CODES SHALL BE STATED
 ON PLANS FOR RELEVANT DESIGN.
 FBC 2004 W/2007 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 2) NOTE: PLEASE SEE FS 481.219 FOR POSSIBLE FICTITIOUS
 NAME FOR ARCHITECT.
 PLEASE COMPLETE INFORMATION ON TITLE BLOCKS PER FAC
 61G1-16.004
  
 3) NOTE: PLEASE COMPLETE ALL CIRCUITING ON PLANS AND
 CORRELATE WITH THE PANEL SCHEDULE.
 PLEASE SEE 240.4, 310.16, 408.4
 FBC 106.3.5.1.2 (ADDITIONAL INFORMATION).
  
 4) NOTE: PLEASE SEE SOME CIRCUITS ON PANEL SCHEDULE AS
 SHOWN DO NOT COMPLY WITH THE NEC. FOR EXAMPLE: PLEASE
 SEE WATER HEATER WHICH IS SHOWN AS 4500VA LOAD YET THIS
 IS ONLY SHOWN ON A SINGLE POLE 25AMP BRANCH CIRCUIT.
 PLEASE SEE 422.13, 240.4, 310.16 ETC
  
 5) NOTE: PLEASE SEE NFPA-72 FOR DEFINITIONS OF SMOKE
 DETECTION DEVICES.
 PLEASE SEE THE PLANS CALL FOR *SMOKE DETECTORS* AND BY
 DEFINITION THIS WOULD MEAN THESE ARE PART OF A FIRE
 ALARM SYSTEM. SMOKE DETECTORS ONLY DETECT AND DO NOT
 SOUND WARNING. PLEASE SEE BASED ON PLANS AND PANEL
 SCHEDULE IT SEEMS THESE ARE *SMOKE ALARMS* WHICH
 ACTUALLY DETECT AND SOUND AND ALARM.
 PLEASE CLARIFY AND COMPLETE.
  
 6) NOTE: PLEASE SEE 210.12 AS ARC FAULT PROTECTION IS
 REQUIRED FOR ALL BRANCH CIRCUITS/OUTLETS IN SLEEPING
 ROOMS.
 PLEASE SEE ONLY ONE BRANCH CIRCUIT FOR SMOKE DETECTION
 TYPE DEVICES SHOWS AFCI BREAKER.
 PLEASE ADJUST AND LIST ALL CIRCUITS REQUIRED.
  
 7) NOTE: PLEASE SEE 210.52B1, 210.11C1 AND 220.53 FOR
 SMALL APPLIANCE CIRCUITS ALONG WITH DINING AREAS AND
 AREAS OF THE LIKE.
  
 8) NOTE: PLEASE CLARIFY IF THE PANEL SHOWN ON PLANS IS
 NEW OR ALREADY EXIST? SHOWN ON PLANS AS NEW YET NO
 CONDUCTORS FOR NEW OR EXISTING FEEDERS IS SHOWN.
 240.4, 310.16 ETC
  
 9) NOTE: PLEASE SEE NFPA-72 11.8.3 FOR SMOKE DETECTION
 DEVICE LOCATIONS. PLEASE SEE NO DEVICES SHALL BE WITHIN
 3FT OF DOORS TO BATHROOMS.
 PLEASE SEE OTHER REQUIRED DISTANCES AND ALSO SPECIFIC
 REQUIREMENTS PER THE MANUFACTURE.
 110.3
  
 10) NOTE: PLEASE SEE 210.11C3 FOR MISSING DEDICATED
 BATH CIRCUIT(S).
 MUST BE 20AMP AND #12.
  
 ** PLEASE COMPLETE THE ABOVE AND KNOW AS THERE IS
 INFORMATION NOT YET SHOWN A COMPLETE REVIEW FOR CODE
 COMPLIANCE CAN NOT BE DONE AT THIS TIME.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved