Plan Review Notes For Permit 07100308 |
Permit Number |
07100308 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-11-16 09:46:55 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST | | PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | (F.S.). | | | | MECHANICAL REVISION | | *** DENIED *** | | 1) NEED TO SIZE THE RETURN AIR DUCT FROM THE MIXING BOX | | TO THE 24X12 RETURN AIR GRILL (SECOND FLOOR), SEE 2004 | | WPB AMEND. 106.3.5.4 (10). | | | | 2) NEED TO SHOW THE SUPPLY AIR DUCT FROM THE AIR | | HANDLER TO WERE IT GOES DOWN TO THE FIRST FLOOR BACK | | BEDROOM, SEE 2004 WPB AMEND. 106.3.5.4 (10). | | | | 3) THE MECHANICAL PLANS NEED THE PRINTED NAME AND | | SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN ON | | THEM, SEE W.P.B. AMEND. 106.1.3. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|