Plan Review Notes
Plan Review Notes For Permit 07100265
Permit Number 07100265
Review Stop B
Sequence Number 2
Notes
Date Text
2007-10-20 16:25:16BUILDING PLAN REVIEW
 PERMIT: 07100265
 ADD: 300 S. AUSTRALIAN AVE #1011
 CONT: AGILE CONST. CORP.
 TEL: (561) 252-0294
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 2ND 10/20/07
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1B)106.1.1* W.P.B. ADMINISTRATIVE CODE/2004 DRAWINGS
 & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO
 THE TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR
 IN PART, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE USED
 AS A SUBSTITUTE FOR SPECIFIC INFORMATION". CONSTRUCTION
 DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
  
 1C) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 2)FBC 106.1.1 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAILTHAT IT WILL CONFORM TO
 THE PROVISIONS? OF THIS CODE AND RELEVANT LAWS. IF THE
 DESIGN PROFESSIONAL IS AND ARCHITECT OR ENGINEER
 LEGALLY REGISTERED UNDER THE LAWS OF THIS STATE, THEN,
 HE/SHE SHALL AFFIX HIS OR HER SEAL, SIGNATURE, LICENSE
 NUMBER AND DATE TO THE DRAWINGS IN ACCORDANCE WITH
 FLORIDA STATUTES CHAPTER 471 AND 481.
 **PROVIDE A WALL DETAIL INDICATING THE STUD TYPE AND
 SPACING OF THE NEW WALLS. A FRAMING DETAIL OF THE
 CEILING IS ALSO REQUIRED SHOWING ALL MATERIALS. THE
 DRAWINGS SHALL BE DRAFTSMAN QUALITY DRAWINGS.**
  
 3)2004 FBC EXISTING: 301.5 A DESIGN PROFESSIONAL OR
 AN OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF
 THIS CODE.
  
 4)N/A
  
 5)OK
  
 6)N/A
 7)N/A
  
 **WPB AMENDMENTS 106.1.3 BUILDING PLANS SHALL BE DRAWN
 TO A MINIMUM 1/8 SCALE AND INDICATE CLEARLY THE AREA OF
 THE WORK PROPOSED. DEPARTMENT POLICY AND STANDARDS FOR
 PLANS AND SPECIFICATIONS PROHIBIT HAND WRITING ON SUCH
 INFORMATION WHICH RELATE TO OUR RECORD MANAGEMENT.
  
 **ALL PLANS SUBMITTED AFTER OCTOBER, 1, 2004 SHALL BE
 DESIGNED TO THE 2004 FLORIDA BUILDING CODE WITH THE
 2006 REV..**
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  