2007-10-15 15:31:57 | *****DENIED***** | | | | NOT ENOUGH INFORMATION TO CONDUCT A THOROUGH FIRE PLAN | | REVIEW | | | | | | 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | 2.COMBUSTIBLE WASTE MATERIAL, DUST, AND DEBRIS SHALL | | BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR | | MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. | | | | 3.THE SCOPE OF WORK SHALL NOT INTERFERE OR HINDER | | ACCESS TO/EGRESS FROM THE OTHER TENANT SPACES ON THE | | SAID FLOOR AND/OR THE BUILDING. | | | | 4.THE ADDRESS OF THE PROJECT SITE SHALL BE IN THE | | TITLE BLOCK OF EACH SUBMITTED PLAN SHEET. | | | | 5.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE | | REFERENCED. | | | | 6.SPECIFY THE NEW WALL AND CEILING FINISH MATERIALS | | IN TERMS OF CLASS A, CLASS B, OR CLASS C. | | | | 7.ILLUSTATE THE LOCATION OF EXIT LIGHS, EMERGENCY | | LIGHTS, AND FIRE EXTINGUISHER(S) FOR THIS TENANT | | SPACE. | | | | 8. WILL THE SCOPE OF WORK HAVE CAUSE FOR ANY FIRE | | SPRINKLER AND/OR FIRE ALARM DEVICES TO BE RE-LOCATED OR | | MOMIDIFIED? | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|