Plan Review Notes
Plan Review Notes For Permit 07100263
Permit Number 07100263
Review Stop B
Sequence Number 2
Notes
Date Text
2008-03-06 13:15:282004 FBC EXISTING BUILDING W/2007 REVISIONS ADDITION
  
 DENIED BY BUILDING
  
 1) SUBMIT PRODUCT APPROVALS FOR THE STOREFRONTS AND
 GLAZING THAT IS SHOWN IN THE DRAWINGS ATTACHED TO THE
 ENGINEERED ALUMINUM FRAME STRUCTURE AND THE EXISTING
 CONCRETE WALLS, AS REQUIRED BY FAC RULE 9B-72. THE
 PRODUCTS DO NOT HAVE TO MEET IMPACT REQUIREMENTS,
 HOWEVER THEY ARE REQUIRED TO MEET THE WIND LOAD
 (COMPONENT & CLADDING) PRESSURES FOR THE STRUCTURE.
  
 2) PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO
 COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE.
  
 3) FBC 106.3* CITY AMENDMENTS PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]