Notes
Date Text
2007-11-06 07:44:09 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
 ALL COMMENTS RELATE TO SHEET 3 3, UNLESS OTHERWISE
 NOTED. ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS
 OTHERWISE NOTED.
  
 THESE COMMENTS WERE NOT CORRECTLY ADDRESSED TO INDICATE
 COMPLIANCE WITH THE CODE;
  
 2} THE SCOPE OF THE ELECTRICAL WORK IS NOT CLEAR ON
 THE PLAN. INDICATE IF THE SERVICE IS NEW OR EXISTING IN
 WHOLE OR IN PART. HAND DRAWN CHANGES TO THE PLAN ARE
 NOT ACCEPTABLE FOR RECORD RETENTION OR CLARITY IN THE
 FIELD. 106.1.3 FBC AS AMENDED. * THERE IS STILL NO
 INDICATION REGARDING IF THE SERVICE IS NEW OR
 EXISTING.
  
 4} IF THE SERVICE IS NEW, PER 110.9 AND 110.10: OBTAIN
 THE AVAILABLE FAULT CURRENT AT THE UTILITY AND
 CALCULATE THE SAME AT THE EQUIPMENT. INDICATE THE AIC
 RATING FOR THE EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT. * NOT ADDRESSED.
  
 5} THE GROUNDING ELECTRODE CONDUCTOR MUST COMPLY WITH
 250.66, AND 250.50. INDICATE SAME ON THE RISER
 DIAGRAM.* NO SIZING GIVEN.SEE ARTICLE.
  
 7} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A)(1) AND
 210.52(A)(2). 2005 NEC. SEE REVIEWED PLAN FOR
 DEFICIENCIES. * SEE KITCHEN
  
 8} LOCATE AND INDICATE A DISCONNECTING MEANS FOR THE
 WATER HEATER. SEE 422.16 NEC FOR CORD AND PLUG
 RESTRICTIONS, AND 422.31(B) FOR HARDWIRE
 REQUIREMENTS.*WATER HEATERS INDICATE THEY ARE CORD
 CONNECTED TO A 120 VOLT RECEPTACLE. VERIFY.
  
 9} EGRESS LIGHTING IS REQUIRED PER 210.70(A)(2)(B). THE
 FRONT DOES NOT COMPLY.
  
 13} THERE IS APPARENTLY IS AN APARTMENT ATTACHED TO THE
 MAIN HOUSE, BUT THE LOAD CALCULATION FOR THE SERVICE
 DID NOT INCLUDE ANY EQUIPMENT OR BRANCH CIRCUITS
 REQUIRED FOR AN APARTMENT. SHOW ALL CALCULATIONS PER
 220 NEC IF CHANGING THE SERVICE, AND ALL PANEL
 SCHEDULES PER 408.4 NEC. * THE TOTAL LOAD WAS NOT
 CALCULATED FOR THE SERVICE PER 220.83, BUT RATHER PER
 PANEL. THE CONDUIT AND CONDUTOR SIZES FOR THE RISER
 DIAGRAM ARE NOT INDICATED, THEREFORE THE SIZE OF THE
 SERVICE CANNOT BE DETERMINED.
  
 NEW COMMENTS THIS REVIEWDUE TO CHANGES IN THE PLAN,
 SPECIFICALLY THE RISER NOW BEING SHOWN AS PART OF THE
 SCOPE;
  
 1} THE RISER SHOWS TWO PANELS. THE FLOOR PLAN SHOWS TWO
 PANELS AT THE METERS AND ONE PANEL IN THE MAIN HOUSE,
 PLEASE CORRELATE.
  
 2} THERE IS NO BATH RECEPTACLE SHOWN IN PANEL "B" PER
 210.11(C)(3)
  
 TO EXPEDITE REVIEW AND CLARIFY THE DESIGNERS INTENT ON
 THE ABOVE ISSUES, SUBMIT WRITTEN RESPONSE TO THE
 COMMENTS MADE IN THIS REVIEW.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]