Plan Review Notes
Plan Review Notes For Permit 07100220
Permit Number 07100220
Review Stop P
Sequence Number 1
Notes
Date Text
2007-10-24 15:17:24DENIED;
 NOT ENOUGH INFORMATION TO DO A PLUMBING PLAN REVIEW. ON
 PERMIT APPLICATION ( DESCRIPTION SECTION)" REPLACE
 C.I AND COPPER WITH PVC".
 THE FOLLOWING IS REQUIRED ON THE PLANS.
 A) A SANITARY RISER DIAGRAM SHOWING ALL PIPE
 SIZES FOR DRAINAGE AND VENTS.
 B) REPLACEMENT OF WATER PIPE, COPPER OR CPVC
 CAN BE USED, NOT PVC FBC PLUMBING SECTION 605.3.
 IS THE HOUSE AND THE APARTMENT ON ONE WATER
 METER? IF SO A BACKFLOE PREVENTOR IS REQUIRED AT THE
 METER. PLEASE SHOW ON PLANS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695