2007-10-11 07:36:12REROOF CONCRETE TILE TO ASPHALT SHINGLE
 2004 FBC WITH 2007 REVISIONS.
  
 DENIED BY BUILDING
  
 1) THE FLORIDA PRODUCT APPROVAL COVER SHEET IS FOR A
 DIFFERENT SHINGLE THAN THE ONE IN THE NOA THAT WAS
 SUBMITTED. PLEASE CORRECT.
  
 2) FBC R905.2.2 REQUIRES TWO LAYERS OF UNDERLAYMENT FOR
 ROOF SLOPES LESS THAN 4 : 12. SPECIFY ON APPLICATION.
  
 3) EFFECTIVE OCTOBER 1, 2007 FLORIDA STATUTE 553.844
 REQUIRES A SECONDARY WATER BARRIER TO BE INSTALLED WHEN
 A ROOF ON AN EXISTING SITE-BUILT, SINGLE FAMILY
 RESIDENTIAL STRUCTURE IS REPLACED. SPECIFY WHICH ONE OF
 THE FOLLOWING REQUIRED METHODS WILL BE INSTALLED.A)
 ALL JOINTS IN ROOF SHEATHING OR DECKING SHALL BE
 COVERED WITH A MINIMUM 4 IN. WIDE STRIP OF
 SELF-ADHERING POLYMER MODIFIED BITUMEN TAPE APPLIED
 DIRECTLY TO THE SHEATHING OR DECKING. THE DECK AND SELF
 ADHERING POLYMER MODIFIED BITUMEN TAPE SHALL BE COVERED
 WITH ONE OF THE UNDERLAYMENT SYSTEMS APPROVED FOR THE
 PARTICULAR ROOF COVERING TO BE APPLIED TO THE ROOF. B)
 THE ENTIRE ROOF DECK SHALL BE COVERED WITH AN APPROVED
 SELF-ADHERING POLYMER MODIFIED BITUMEN CAP SHEET. NO
 ADDITIONAL UNDERLAYMENT SHALL BE REQUIRED ON TOP OF
 THIS CAP SHEET FOR NEW INSTALLATIONS. EXCEPTIONS: 1. AN
 ASPHALT IMPREGNATED 30# FELT UNDERLAYMENT INSTALLED
 WITH NAILS AND TIN-TABS AS REQUIRED FOR THE HVHZ AND
 COVERED WITH EITHER AN APPROVED SELF-ADHERING POLYMER
 MODIFIED BITUMEN CAP SHEET OR AN APPROVED CAP SHEET
 APPLIED USING AN APPROVED HOT-MOP APPLICATION SHALL BE
 DEEMED TO MEET THE REQUIREMENTS FOR THE SECONDARY WATER
 BARRIER.
  