Plan Review Notes
Plan Review Notes For Permit 07100208
Permit Number 07100208
Review Stop B
Sequence Number 2
Notes
Date Text
2007-11-06 10:28:38****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.SHUTTER CONNECTION MOUNTING TYPE SHOULD CORRELATE
 WITH THE ANCHOR SCHEDULE; IN THIS CASE, C1 THROUGH C5.
  
  
 2.ANCHOR TYPE IS TO BE SPECIFIC.THE 12" SPACING ON
 THE INSTALLATION SCHEDULE IS NOT COMPLIANT FOR ANY OF
 THE CONNECTION TYPES FOR ITW TAPCON, AND NOT COMPLIANT
 FOR SOME CONNECTION TYPES FOR THE OTHER TAPCONS.SEE
 SHEET 8.
  
 3.PLEASE NOTE THAT SUBSTRATE ON THE INSTALLATION
 SCHEDULE IS TO BE SUBSTRATE OF THE OPENING, TOP AND
 BOTTOM, NOT CONSTRUCTION OF THE BUILDING.