Plan Review Notes For Permit 07100201 |
Permit Number |
07100201 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-10-18 17:04:56 | *****PROVISO***** | | | | PLANS TO BE FIRE STAMPED UPON ACKNOWLEDGEMENT OF THE | | FOLLOWING: | | | | 1.THE REMOVAL AND/OR THE STOCKING OF BUILDING | | MATERIALS & SUPPLIES SHALL NOT INTERFERE OR HINDER | | ACCESS TO/EGRESS FROM THE SAID FLOOR OR BUILDING. | | | | 2.ON SHEET E-2, A CARD READER (CR) AND ELECTRIC LOCK | | (EL) ARE NOTED FOR THE NEW DOOR (1202) .WILL THERE BE | | ANY IMPACT TO EGRESSING FROM THE OPEN OFFICE AREA, AND | | IF SO, HOW WILL THE CRITERIA AS PER NFPA 101 - | | 7.2.1.6.2 BE ACHIEVED? | | | | 3.SPECIFY THE NEW WALL INTERIOR FINISH MATERIAL IN | | TERMS OF CLASS A, CLASS B, OR CLASS C. | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING WHERE ON THE PLAN EACH COMMENT WAS | | ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|