2007-10-14 12:23:57 | ** DENIED ** |
| |
| 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH |
| ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS |
| UNDER THE NEW CODES ADOPTED BY THE STATE. |
| PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| AFFECT DESIGNS FOR ALL TRADES. |
| PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| REVIEWER AT A MINIMUM. |
| 2004 FBC W/ 2006 REVISIONS |
| 2005 NFPA-70**2002 IS STATED ON PLANS/IN NOTES ON |
| E-1* |
| 2002 NFPA-72 |
| 2003 NFPA-101 |
| |
| ** PLEASE SEE ANY OTHER COMMENTS FROM OTHER TRADES SUCH |
| AS BUILDING AS THE *LEVEL OF ALTERATION* PER FBC |
| EXISTING BUILDING CODE DOES REQUIRE LEVEL TO BE |
| STATED. |
| |
| 2) NOTE: PLEASE SEE THE APPLICATION WAS ROUTED TO THE |
| ADDRESSING REVIEWER AS THE PERMIT APPLICATION IS FOR |
| 12TH FLOOR AND NO UNIT/SUITE WAS APPLIED OR GIVEN. |
| THE LOCATION AS ASSESSED AT TIME OF APPLICATION DOES |
| NOT PLACE PROJECT IN *EAST* TOWER NOR DOES HAS A |
| UNIT/SUITE NUMBER BEEN GENERATED. |
| ONCE ANY SUITE/UNIT NUMBER HAS BEEN ASSIGNED, PLEASE BE |
| SURE TO ADD TO TITLE BLOCKS. |
| |
| 3) NOTE: PLEASE CORRELATE ELECTRICAL LIGHTING FIXTURES |
| ON PLANS WITH THAT OF THE DESIGNATIONS AS SHOWN ON |
| FIXTURE LEGEND. PLEASE SEE THE PLANS SHOW SOME FIXTURE |
| SYMBOLS WHICH ARE NOT ON THE FIXTURE LEGEND. (HALF |
| DARKENED RECESSED LTS) ARE THESE NEW? EXISTING? |
| FBC 106.1.2 |
| PLEASE KNOW, *IF NEW*, NEED TO PROVIDE MAXIMUM LIGHTING |
| PERFORMANCE CALCULATIONS PER 13-415.2 AND CONTROLS PER |
| 13-101, 13-415.1.ABC.1.1, .1.2. |
| IF ALL EXISTS PLEASE MATCH TYPES AND INDICATED AS |
| SUCH. |
| |
| ** ALL LIGHTING AND CONTROLS WHICH ARE SHOWN APPEAR TO |
| BE EXISTING WITH ONLY ONE NEW FIXTURE BEING ADDED. CAN |
| NOT CONFIRM AT THIS TIME. |
| |
| ** PLEASE ADDRESS THE ABOVE COMMENTS. IF THERE ARE ANY |
| QUESTIONS, PLEASE DO NOT HESITATE IN CONTACTING THIS |
| OFFICE. |
| |
| ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES |
| WHICH MAY AFFECT ELECTRICAL PLANS. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |