2007-10-17 15:49:57 | DENIED |
| REFERENCE: |
| ** FBC-2004 WITH 05 & 06 REVISIONS, PLUMBING. |
| ** FBC-2004 CHAPTER 1, THE CITY OF |
| WEST PALM BEACH AMENDMENTS. |
| ** FLORIDA ADMINISTRATIVE CODE (FAC). |
| ** FLORIDA STATUTES (FS). |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE: |
| |
| 1. NOTE: SHEET 1, OF THE SUBMITTED PLANS HAVE AN |
| ARCHITECTURAL TITLE BLOCK FROM EVERETT H JENNER |
| AR-0007573, PER FAC-CODE-61G1-16001 ARCHITECT'S AND |
| INTERIOR DESIGNER'S SEAL: |
| EACH ARCHITECT AND INTERIOR DESIGNER |
| SHALL ACQUIRE A SEAL WITH WHICH HE OR |
| SHE SHALL IDENTIFY ALL PLANS, |
| SPECIFICATIONS OR REPORTS PREPARED OR |
| ISSUED BY HIM OR HER AND FILED FOR |
| PUBLIC RECORD. THE SEAL SHALL BE OF A |
| TYPE WHICH WILL MAKE AN IMPRESSION ON |
| THE SURFACE OF PRINTS OR OTHER |
| DUPLICATIONS OF DRAWINGS, AND AS |
| APPROPRIATE, UPON SPECIFICATION PAGES, |
| AND OTHER ARTICLES OF SERVICE. |
| |
| 2. PER FBC-2004 CHAPTER 1, SECTION 106.1.2 PLEASE |
| SUBMIT ADDITIONAL DATA PER THE FOLLOWING FBC-2004 W/ |
| 06, REV. PLUMBING, CODE SECTIONS, 601.1 WATER SUPPLY |
| DESIGN (IRRIGATION), 608, POTABLE WATER PTOTECTION, AND |
| 305.3 STRESS AND STRAIN. |
| |
| A} 601.1 & 608: CLEARLY INDICATE THE BACKFLOW |
| PREVENTER LOCATION ON THE RESUBMITTED PLANS AND PROVIDE |
| A SYMBOL FOR IT IN THE IRRIGATION LEGEND. |
| |
| B} 601.1 & 608: CLEARLY INDICATE IF THE BACKFLOW |
| PREVENTER IS EXISTING OR NEW ON THE RESUBMITTED PLANS. |
| |
| |
| C} 305.3: CLEARLY INDICATE ON THE RESUBMITTED PLAN ALL |
| REQUIRED SLEEVE LOCATIONS FOR THE IRRIGATION PIPING IN |
| PARKING LOTS, AND SIDEWALK AREAS. |
| |
| END OF COMMENTS: |
| |