2007-10-16 10:12:50 | **** DENIED **** |
| |
| |
| 1) NOTE:PLEASE BE SURE ALL OF THE FOLLOWING RELEVANT |
| CODES ARE STATED ON PLANS. |
| PLEASE KNOW THAT ALL PERMIT APPLICATIONS DATED AFTER |
| DECEMBER 8TH, 2006 FALL UNDER THE FOLLOWING CODES AT A |
| MINIMUM. |
| PLEASE BE AWARE OF ANY OTHER CODES WHICH MAY BE |
| REFERENCED BY OTHER TRADES DURING THEIR REVIEW. THE |
| FOLLOWING IS NEEDED ON ELECTRICAL SHEETS AS WELL AS |
| FIRE ALARM SHEETS BY THIS REVIEWER AT A MINIMUM. |
| 2004 FBC W/ 2006 REVISIONS. |
| 2005 NFPA-70 |
| |
| ** PLEASE BE SURE TO SEE COMMENTS FROM OTHER TRADES FOR |
| CODES. |
| |
| 2) NOTE: PLEASE SUBMIT PLANS WHICH ARE NOT DONE IN |
| PEN/PENCIL. PLEASE SEE MINIMUM CONSTRUCTION DOCUMENTS |
| STANDARDS PER FBC 106.1 |
| |
| 3) NOTE: PLEASE SUBMIT ELECTRICAL WITH MORE DETAIL FOR |
| NEW ELEVATOR. THIS NEEDS TO INCLUDE SIZE OF MOTOR, |
| LOADS, ETC. |
| THE OVER CURRENT PROTECTION WHICH IS SHOWN AS EXISTING |
| ALONG WITH CONDUCTOR SIZES CAN NOT BE VERIFIED FOR |
| MOTOR AT THIS TIME. |
| PLEASE SEE THAT STATING SOME OF THE CODES IN LIEU OF |
| SPECIFIC DETAIL CAN NOT BE ACCEPTED. |
| PLEASE SEE THERE ARE SEVERAL SECTIONS OF NEC 620 WHICH |
| INFORMATION IS NEEDED. DISCONNECT LOCATIONS FOR BRANCH |
| CIRCUITS; MOTORS ETC ARE REQUIRED TO BE GROUPED IN ONE |
| LOCATION. |
| PLEASE SEE PLANS ARE MISSING AN EQUIPMENT ROOM, PIT, |
| AND OTHER ITEMS WHICH ARE NOT CLEAR IF THESE WILL BE |
| REQUIRED. |
| THERE IS A STRUCTURAL SHEET WHICH DOES SHOW A LAYOUT |
| FOR EQUIPMENT HOWEVER THIS DOES NOT CORRELATE WITH |
| ELECTRICAL PLANS. |
| PLEASE SEE THE ELECTRICAL DETAILS ON SHEETS DO NOT |
| CORRELATE WITH THE ELECTRICAL DONE BY THE ELECTRICAL |
| CONTRACTOR. THIS SHOWS 3-POLE BREAKERS AND ELECTRICAL |
| BY CONTRACTOR SHOWS 2-POLE BREAKERS. |
| PLEASE SUBMIT COMPLETE ELECTRICAL PLANS SHOWING LAYOUT |
| OF ALL EQUIPMENT. PLEASE INCLUDE ALL DETAILS. |
| FBC 106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION. |
| NEC 430, 620, 310.16, 240.4 ETC |
| |
| 4) NOTE: PLEASE SEE SHEET WHICH CONTAINS THE ELECTRICAL |
| EQUIPMENT LAYOUT DOES NOT CONTAIN ANY TITLE BLOCK ALONG |
| WITH OTHER SHEETS WHICH ARE SIGNED, DATED AND SEALED BY |
| THE ENGINEER. |
| FAC 61G15-23.002 |
| |
| 5) NOTE: PLEASE VERIFY WITH THE STATE ANY POSSIBLE |
| REQUIREMENTS FOR A/C TO BE PLACED IN THE EQUIPMENT |
| ROOM. THIS HAS COME TO OUR ATTENTION THAT THIS IS BEING |
| REQUIRED AT SEVERAL LOCATIONS. |
| THIS IS NOTED FOR INFORMATION ONLY. |
| |
| ** PLEASE KNOW AS THERE ARE SEVERAL ITEMS NOT YET |
| COMPLETED ON PLANS FOR REVIEW, NOT ALL COMMENTS MAY BE |
| PRESENT AT THIS TIME. |
| |
| |
| ** PLEASE SEE COMMENTS FROM OTHER TRADES WHICH WILL |
| AFFECT PLANS, SUBMITTED DOCUMENTS AND ELECTRICAL |
| PLANS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |