Plan Review Notes
Plan Review Notes For Permit 07100169
Permit Number 07100169
Review Stop E
Sequence Number 1
Notes
Date Text
2007-10-16 10:12:50**** DENIED ****
  
  
 1) NOTE:PLEASE BE SURE ALL OF THE FOLLOWING RELEVANT
 CODES ARE STATED ON PLANS.
 PLEASE KNOW THAT ALL PERMIT APPLICATIONS DATED AFTER
 DECEMBER 8TH, 2006 FALL UNDER THE FOLLOWING CODES AT A
 MINIMUM.
 PLEASE BE AWARE OF ANY OTHER CODES WHICH MAY BE
 REFERENCED BY OTHER TRADES DURING THEIR REVIEW. THE
 FOLLOWING IS NEEDED ON ELECTRICAL SHEETS AS WELL AS
 FIRE ALARM SHEETS BY THIS REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70
  
 ** PLEASE BE SURE TO SEE COMMENTS FROM OTHER TRADES FOR
 CODES.
  
 2) NOTE: PLEASE SUBMIT PLANS WHICH ARE NOT DONE IN
 PEN/PENCIL. PLEASE SEE MINIMUM CONSTRUCTION DOCUMENTS
 STANDARDS PER FBC 106.1
  
 3) NOTE: PLEASE SUBMIT ELECTRICAL WITH MORE DETAIL FOR
 NEW ELEVATOR. THIS NEEDS TO INCLUDE SIZE OF MOTOR,
 LOADS, ETC.
 THE OVER CURRENT PROTECTION WHICH IS SHOWN AS EXISTING
 ALONG WITH CONDUCTOR SIZES CAN NOT BE VERIFIED FOR
 MOTOR AT THIS TIME.
 PLEASE SEE THAT STATING SOME OF THE CODES IN LIEU OF
 SPECIFIC DETAIL CAN NOT BE ACCEPTED.
 PLEASE SEE THERE ARE SEVERAL SECTIONS OF NEC 620 WHICH
 INFORMATION IS NEEDED. DISCONNECT LOCATIONS FOR BRANCH
 CIRCUITS; MOTORS ETC ARE REQUIRED TO BE GROUPED IN ONE
 LOCATION.
 PLEASE SEE PLANS ARE MISSING AN EQUIPMENT ROOM, PIT,
 AND OTHER ITEMS WHICH ARE NOT CLEAR IF THESE WILL BE
 REQUIRED.
 THERE IS A STRUCTURAL SHEET WHICH DOES SHOW A LAYOUT
 FOR EQUIPMENT HOWEVER THIS DOES NOT CORRELATE WITH
 ELECTRICAL PLANS.
 PLEASE SEE THE ELECTRICAL DETAILS ON SHEETS DO NOT
 CORRELATE WITH THE ELECTRICAL DONE BY THE ELECTRICAL
 CONTRACTOR. THIS SHOWS 3-POLE BREAKERS AND ELECTRICAL
 BY CONTRACTOR SHOWS 2-POLE BREAKERS.
 PLEASE SUBMIT COMPLETE ELECTRICAL PLANS SHOWING LAYOUT
 OF ALL EQUIPMENT. PLEASE INCLUDE ALL DETAILS.
 FBC 106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION.
 NEC 430, 620, 310.16, 240.4 ETC
  
 4) NOTE: PLEASE SEE SHEET WHICH CONTAINS THE ELECTRICAL
 EQUIPMENT LAYOUT DOES NOT CONTAIN ANY TITLE BLOCK ALONG
 WITH OTHER SHEETS WHICH ARE SIGNED, DATED AND SEALED BY
 THE ENGINEER.
 FAC 61G15-23.002
  
 5) NOTE: PLEASE VERIFY WITH THE STATE ANY POSSIBLE
 REQUIREMENTS FOR A/C TO BE PLACED IN THE EQUIPMENT
 ROOM. THIS HAS COME TO OUR ATTENTION THAT THIS IS BEING
 REQUIRED AT SEVERAL LOCATIONS.
 THIS IS NOTED FOR INFORMATION ONLY.
  
 ** PLEASE KNOW AS THERE ARE SEVERAL ITEMS NOT YET
 COMPLETED ON PLANS FOR REVIEW, NOT ALL COMMENTS MAY BE
 PRESENT AT THIS TIME.
  
  
 ** PLEASE SEE COMMENTS FROM OTHER TRADES WHICH WILL
 AFFECT PLANS, SUBMITTED DOCUMENTS AND ELECTRICAL
 PLANS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  