Plan Review Notes For Permit 07100133 |
Permit Number |
07100133 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-10-18 19:25:34 | *****DENIED***** | | | | 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | 2.DURING SCOPE OF WORK ALL REQUIRED EXIT COMPONENTS, | | FIRE RESISTIVE ASSEMBLIES, AND FIRE PROTECTION SYSTEMS | | SHALL BE MAINTAINED.SHALL BE MAINTAINED. | | | | 3.WHEN/IF IT IS NECESSARY TO SHUT DOWN THE SPRINKLER | | SYSTEM FOR THE RELOCATION OF DEVICE(S), THE FIRE | | DEPARTMENT WILL BE NOTIFIED WHEN IT IS SHUT DOWN AND | | WHEN IT IS RETURNED TO SERVICE. | | | | 4.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE | | REFERENCED. | | | | 5.SPECIFY THE NEW WALL INTERIOR FINISH MATERIAL IN | | TERMS OF CLASS A, CLASS B, OR CLASS C. | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING WHERE ON THE PLAN EACH COMMENT WAS | | ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|