Plan Review Notes For Permit 07100133 |
Permit Number |
07100133 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-10-14 10:16:49 | ** DENIED ** | | | | 1) NOTE: PLEASE SEE NO CODES AND SCOPE OF WORK IS SHOWN | | ON PLANS FOR DESIGN. | | FBC 106.1.2, 106.3.5.1.2, 110.1.2 | | | | NFPA-70 2005 | | NFPA-72 2002 | | NFPA-101 2003 | | FBC 2004 W/2006 REVS. | | | | ** THESE ARE REQUIRED AT A MINIMUM, SEE COMMENTS FROM | | OTHER TRADES FOR OTHER POSSIBLE CODES. | | | | 2) NOTE: NOTE ON PLANS MENTIONS THE EXISTING PANEL IS | | CAPABLE OF THE ADDITIONAL LOAD, HOWEVER NO INFORMATION | | FOR EXISTING LOAD WITH NEW LOAD OR SIZE OF THIS | | EXISTING PANEL WAS GIVEN. | | FBC 106.3.5.1.2, 16.1.2 | | NEC. 220 | | | | | | * ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR | | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL | | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS | | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT | | LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | SHOULD BE SUBMITTED FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY | | DELAYS. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|