Plan Review Notes
Plan Review Notes For Permit 07100133
Permit Number 07100133
Review Stop E
Sequence Number 1
Notes
Date Text
2007-10-14 10:16:49** DENIED **
  
 1) NOTE: PLEASE SEE NO CODES AND SCOPE OF WORK IS SHOWN
 ON PLANS FOR DESIGN.
 FBC 106.1.2, 106.3.5.1.2, 110.1.2
  
 NFPA-70 2005
 NFPA-72 2002
 NFPA-101 2003
 FBC 2004 W/2006 REVS.
  
 ** THESE ARE REQUIRED AT A MINIMUM, SEE COMMENTS FROM
 OTHER TRADES FOR OTHER POSSIBLE CODES.
  
 2) NOTE: NOTE ON PLANS MENTIONS THE EXISTING PANEL IS
 CAPABLE OF THE ADDITIONAL LOAD, HOWEVER NO INFORMATION
 FOR EXISTING LOAD WITH NEW LOAD OR SIZE OF THIS
 EXISTING PANEL WAS GIVEN.
 FBC 106.3.5.1.2, 16.1.2
 NEC. 220
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]