| BUILDING PLAN REVIEW |
| PERMIT: 07100133 |
| ADD: 401 N. DIXIE HWY 5TH FL #5259 |
| CONT: H.A. CONTRACTING CORP. |
| TEL: (305)591-9212 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2006 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVIEW: 1ST |
| ACTION: DENIED |
| 10/13/07 |
| |
| 1A)--- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| YOUR ANTICIPATED COOPERATION. |
| |
| 1B)106.1.1* W.P.B. ADMINISTRATIVE CODE/2004 DRAWINGS |
| & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM |
| OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, |
| WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE |
| TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO |
| THE TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR |
| IN PART, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE USED |
| AS A SUBSTITUTE FOR SPECIFIC INFORMATION". CONSTRUCTION |
| DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE |
| LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND |
| SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS |
| OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND |
| REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL. |
| |
| 2)2004 FBC EXISTING |
| 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE |
| OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO |
| SECTIONS 303, 304 AND 305 OF THIS CODE. |
| |
| 3)110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION |
| THAT IS REQUIRED FOR RECORD KEEPING A) THE EDITION OF |
| THE CODE UNDER WHICH THE PROJECT IS DESIGNED. |
| B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE |
| PROVISIONS OF CHAPTER 3. |
| C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6, |
| TABLE 601. |
| D) THE OCCUPANT LOAD, SEE 1004. |
| E) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED |
| F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED. |
| 4)TABLE 803.3 MINIMUM INTERIOR FINISH CLASSIFICATION; |
| PROVIDE INFORMATION BASED ON INTERIOR FINISH |
| REQUIREMENTS BASED ON OCCUPANCY. |
| |
| 5)INDICATE THE TYPE OF GLASS TO BE INSTALLED AT THE |
| NEW WINDOW OPENING PER FBC 2406. |
| |
| MYRON JACOBS |
| BUILDING PLAN REVIEWER |