Plan Review Notes
Plan Review Notes For Permit 07100119
Permit Number 07100119
Review Stop E
Sequence Number 4
Notes
Date Text
2007-12-28 11:11:15NOTE ADDED, PLANS ROUTED TO ZONING AS SETS HAVE NEW
 SHEETS A-1 AND A-3, NEEDS NEW STAMPS.
2007-12-28 11:10:18 
 *** PROVISO/REVISION ***
  
 ** PLEASE SEE THE FOLLOWING ITEMS WHICH ARE TO BE
 REVISED BEFORE ANY ROUGH ELECTRICAL INSPECTION.
  
 1) NOTE: PLEASE SEE THE MAXIMUM TIME ON OVER RIDE
 OCCUPANCY SENSOR IS 30MINS. SHOWN AS MINIMUM TIME.
 13-415.1.ABC.1.1, .1.2
  
 2) NOTE: PLEASE REVISE PANEL SCHEDULE ON M/E SHEET
 SHOWING THE CORRECTED MAIN CIRCUIT BREAKER, PANEL SIZE
 AND BRANCH CIRCUITS.
 THE CONDUCTORS NOW SHOWN ON PANEL SCHEDULE FOR RTU IS
 NOT THE SAME AS RISER. RISER SHOWS #4 AND PANEL
 SCHEDULE NOW SHOWS #2.
 240.4, 310.16, 408.4
  
 3) NOTE: PLEASE SEE BATH ROOMS WHICH STILL SHOW ONLY
 STANDARD SWITCHES. PLEASE KNOW IF THESE ARE NEW MUST
 MEET 13-415.1ABC.1.2.
  
 4) NOTE: 200AMP MAIN CIRCUIT BREAKER ON NEW PANEL.
 240.4, 310.16, 240.21, 408.36 ETC
 THIS WAS CHANGED BY ENGINEER HOWEVER SHEETS NEED TO BE
 RE-PRINTED.
  
  
 IF THERE ARE ANY QUESTIONS ON THE ABOVE PLEASE DO NOT
 HESITATE IN CONTACTING THIS REVIEWER DIRECTLY.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]