Plan Review Notes
Plan Review Notes For Permit 07100119
Permit Number 07100119
Review Stop E
Sequence Number 3
Notes
Date Text
2007-12-06 10:05:53** DENIED 3RD REVIEW **
  
 ** PLEASE SEE SOME ITEMS FROM TWO PREVIOUS REVIEWS ARE
 STILL IN NEED OF ADDRESSING ALONG WITH NEW COMMENTS DUE
 TO CHANGES MADE TO PLANS.
  
 1) NOTE: PLEASE SEE THE RESPONSE LETTER PROVIDED BY THE
 DESIGN PROFESSIONAL ONLY RESPONDS PART OF THE NOTES
 FROM THE 2ND REVIEW. THE NOTE #1 FROM PREVIOUS REVIEW
 #2 SPECIFICALLY MENTIONED THAT ALL NOTES FROM FIRST
 REVIEW REMAINED WITH THE EXCEPTION OF NOTE #2. PLEASE
 KNOW A RESPONSE LETTER IS NOT REQUIRED ALTHOUGH IS
 HELPFUL IN THE REVIEW PROCESS IF COMPLETE.
  
 2) NOTE: PLEASE SEE NOTE #1 FROM ORIGINAL REVIEW WHICH
 STILL NEEDS ADDRESSING.
 PLEASE LIST ALL RELEVANT CODES ON PLANS.
 2004 FBC W/2007 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72 (WHERE APPLICABLE) AS FIRE ALARM SYSTEM
 HAS NOT BEEN DETERMINED, THIS CODE WILL REMAIN.
  
 2) NOTE: PLEASE SEE PANEL SCHEDULE STILL LIST #8 FOR
 90AMP OVER CURRENT PROTECTION FOR THE RTU. THIS EXCEEDS
 310.16 FOR RATING OF CONDUCTORS.
 PLEASE ALSO SEE THE PANEL LIST THIS AS A 2-POLE WHERE
 SPACES IN PANEL AND CONDUCTORS LEND TO THIS A 3-PHASE?
 240.4, 310.16 ETC
 FBC 106.1.2 FOR COORDINATION.
  
 3) NOTE: PLEASE SEE THE RISER IS MISSING EQUIPMENT
 GROUNDING CONDUCTORS AFTER ALL FIRST MEANS OF
 DISCONNECTS.
 250.110, 250.24, 250.122
  
 4) NOTE: PLEASE SEE NOTES UNDER PERMIT APPLICATION FOR
 OTHER SCOPE OF WORK AT THIS SAME LOCATION AS THE
 SERVICE RISER AS SHOWN CONTAINS SEVERAL NON-CODE
 COMPLIANT ITEMS.
 PLEASE GO OVER THE NEC 2005 AS THE SERVICE WILL BE
 REQUIRED TO MEET THE CURRENT CODE.
 THERE ARE ITEMS ON RISER UNDER THIS REVIEW AND THE
 REVIEW OF THE OTHER APPLIED PERMIT FOR THIS LOCATION
 WHICH NEVER MET THE MINIMUM CODE AS SHOWN.
 PLEASE GIVE MORE DETAILS FOR COMPLETE RISER SHOWING NEW
 AND EXISTING AND ADJUST FOR CODE COMPLIANCE. PLEASE SEE
 SOME EXAMPLES ARE NOTED BELOW:
 PLEASE SEE MISSING EQUIPMENT GROUNDS AS NOTED ABOVE.
 PLEASE SEE THE GROUNDING ELECTRODE CONDUCTOR IS NOT
 LARGE ENOUGH PER 250.66.
 PLEASE SEE 40AMP DISCONNECT STILL SHOWN WITH 5-#8
 CONDUCTORS TO A 2-POLE 40AMPS DISCONNECT IN A 3/4 INCH
 CONDUIT.
 PLEASE SEE NO MAIN FOR TAPPED CONDUCTORS FOR NEW PANEL
 PER 240.21, 310.16, 240.4, 408.36 ETC
 PLEASE SEE 700.12F FOR CIRCUITING OF EMERGENCY AND EXIT
 LIGHTS (THIS WILL BE NOTED BELOW FOR SPACE). PLEASE SEE
 NO PANEL SCHEDULE WAS SUBMITTED FOR HPB, YET THIS PANEL
 IS IN THE NEW TENANT SPACE BEING CREATED. 408.4, 240.4,
 310.16 ETC.
 FBC 106.3.5.1.2, 106.1.2 FOR ADDITIONAL INFORMATION.
  
 5) NOTE: PLEASE SEE FBC 13-101.1, 13-415.1.ABC.1.1,
 .1.2AS NO LIGHTING CONTROLS OR SYSTEM WAS SUBMITTED
 FOR REVIEW. LIGHTING IS NOTED AS *ALL EXISTING* WITH
 NEW CIRCUITS YET NO LIGHTING CONTROLS WERE SUBMITTED.
  
 6) NOTE: PLEASE SEE CIRCUITING PER 700.12F FOR
 EMERGENCY AND EXIT LIGHTS SHALL BE CIRCUITED TO THE
 LOCAL BRANCH CIRCUIT FEEDING LOCAL LIGHTING.
  
 7) NOTE: PLEASE SEE MISSING SHOW WINDOW RECEPTACLES PER
 210.62, 220.43
 THE NEW SIGN CIRCUIT WHICH IS PART OF 600.5 IS NOT THE
 SAME.
  
 8) NOTE: PLEASE SEE TWO SETS OF ENERGY CALCULATIONS
 WERE SUBMITTED SHOWING A METHOD *A* AND METHOD *B*.
 PLEASE SEE THAT METHOD *A* CAN NOT BE USED AS THIS IS
 NOT A *WHOLE BUILDING*.
 PLEASE SEE 13-415.2 AS THIS IS ALREADY A CONDITIONED
 SPACE AND RE-FEEDING THE EXISTING UNIT.
 PLEASE SEE THE ENERGY CALCULATIONS AS SUBMITTED DO NOT
 CONTAIN ANY INPUT DATA REPORTS AS REQUIRED. PLEASE SEE
 PAGE #2 WHICH SPECIFICALLY MENTIONS THAT THE
 CALCULATION SUMMARY SHEETS MUST BE ACCOMPANIED BY THE
 INPUT DATA REPORT.
 PLEASE SEE THE JURISTICTION IS LISTED AS PALM BEACH
 COUNTY.
 WE ARE UNABLE TO REVIEW FOR CODE COMPLIANCE AT THIS
 TIME.
 PLEASE BE SURE TO COMPLETE FIXTURE LEGEND FOR
 FIXTURES.
  
 9) NOTE: PLEASE PROVIDE NEW ROOF-TOP GFI PER 210.63,
 210.8.
 AS THIS IS A NEW TENANT, ANY EXISTING DEVICES WOULD
 NOT BE FED FROM OTHER POWER SOURCE LOCATIONS.
  
 10) NOTE: PLEASE VERIFY PANEL AS SHOWN AS 200AMPS IS
 200AMPS. THIS IS MOST LIKELY A 225AMP AND WILL CONTAIN
 A 200AMP MCB.
 PANEL MENTIONS *FUSED AT DISCONNECT* HOWEVER AS NO
 DISCONNECT IS SHOWN ON RISER THIS IS NOT POSSIBLE.
 PLEASE VERIFY AND ADJUST AS NOTED ABOVE FOR TAPPED
 CONDUCTORS.
 240.21, 310.16, 90.7, 110.3 ETC
 FBC 106.3.5.1.2, 106.1.2 FOR ADDITIONAL INFORMATION.
  
 11) NOTE: PLEASE SEE NO RESPONSE WAS PROVIDED ON
 WHETHER OR NOT THE BUILDING CONTAINS A FIRE ALARM
 SYSTEM?
 PLEASE SEE THE MECHANICAL PLANS INDICATE A NEW HORN
 STROBE FOR UNIT AND AS THIS IS NOT SHOWN ON ELECTRICAL
 IT IS BEING *ASSUMED* THIS IS LOCATED IN SPACE. PLEASE
 KNOW IF ANY FA SYSTEM IS LOCATED OR WILL BE MODIFIED,
 ALL DEVICES SHALL COMPLY WITH FBC 11-4.28.1,.2 AND
 .3(4).
  
 12) NOTE: PLEASE SEE WALL WHICH CONTAINS RECEPTACLES
 WHICH MENTIONS TO PROVIDE EXTENSIONS, HOWEVER NO
 CIRCUITING ON HOW THESE ARE FED IS SHOWN.
 PLEASE ALSO COORDINATE SHEET M-1, E-2 AS THE ELECTRICAL
 SHEETS E-1 ONLY CONTAINS TWO ELECTRICAL PANELS AND E-2
 CONTAINS 3.
 FBC 106.1.2, ADDITIONAL INFORMATION/COORDINATION.
  
 13) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE.
  
 ** PLEASE KNOW THAT A FIELD INSPECTION MAY BE NEEDED TO
 GO OVER EXISTING WORK AND PROPOSED NEW.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  