2007-12-06 10:05:53 | ** DENIED 3RD REVIEW ** |
| |
| ** PLEASE SEE SOME ITEMS FROM TWO PREVIOUS REVIEWS ARE |
| STILL IN NEED OF ADDRESSING ALONG WITH NEW COMMENTS DUE |
| TO CHANGES MADE TO PLANS. |
| |
| 1) NOTE: PLEASE SEE THE RESPONSE LETTER PROVIDED BY THE |
| DESIGN PROFESSIONAL ONLY RESPONDS PART OF THE NOTES |
| FROM THE 2ND REVIEW. THE NOTE #1 FROM PREVIOUS REVIEW |
| #2 SPECIFICALLY MENTIONED THAT ALL NOTES FROM FIRST |
| REVIEW REMAINED WITH THE EXCEPTION OF NOTE #2. PLEASE |
| KNOW A RESPONSE LETTER IS NOT REQUIRED ALTHOUGH IS |
| HELPFUL IN THE REVIEW PROCESS IF COMPLETE. |
| |
| 2) NOTE: PLEASE SEE NOTE #1 FROM ORIGINAL REVIEW WHICH |
| STILL NEEDS ADDRESSING. |
| PLEASE LIST ALL RELEVANT CODES ON PLANS. |
| 2004 FBC W/2007 REVISIONS. |
| 2005 NFPA-70 |
| 2003 NFPA-101 |
| 2002 NFPA-72 (WHERE APPLICABLE) AS FIRE ALARM SYSTEM |
| HAS NOT BEEN DETERMINED, THIS CODE WILL REMAIN. |
| |
| 2) NOTE: PLEASE SEE PANEL SCHEDULE STILL LIST #8 FOR |
| 90AMP OVER CURRENT PROTECTION FOR THE RTU. THIS EXCEEDS |
| 310.16 FOR RATING OF CONDUCTORS. |
| PLEASE ALSO SEE THE PANEL LIST THIS AS A 2-POLE WHERE |
| SPACES IN PANEL AND CONDUCTORS LEND TO THIS A 3-PHASE? |
| 240.4, 310.16 ETC |
| FBC 106.1.2 FOR COORDINATION. |
| |
| 3) NOTE: PLEASE SEE THE RISER IS MISSING EQUIPMENT |
| GROUNDING CONDUCTORS AFTER ALL FIRST MEANS OF |
| DISCONNECTS. |
| 250.110, 250.24, 250.122 |
| |
| 4) NOTE: PLEASE SEE NOTES UNDER PERMIT APPLICATION FOR |
| OTHER SCOPE OF WORK AT THIS SAME LOCATION AS THE |
| SERVICE RISER AS SHOWN CONTAINS SEVERAL NON-CODE |
| COMPLIANT ITEMS. |
| PLEASE GO OVER THE NEC 2005 AS THE SERVICE WILL BE |
| REQUIRED TO MEET THE CURRENT CODE. |
| THERE ARE ITEMS ON RISER UNDER THIS REVIEW AND THE |
| REVIEW OF THE OTHER APPLIED PERMIT FOR THIS LOCATION |
| WHICH NEVER MET THE MINIMUM CODE AS SHOWN. |
| PLEASE GIVE MORE DETAILS FOR COMPLETE RISER SHOWING NEW |
| AND EXISTING AND ADJUST FOR CODE COMPLIANCE. PLEASE SEE |
| SOME EXAMPLES ARE NOTED BELOW: |
| PLEASE SEE MISSING EQUIPMENT GROUNDS AS NOTED ABOVE. |
| PLEASE SEE THE GROUNDING ELECTRODE CONDUCTOR IS NOT |
| LARGE ENOUGH PER 250.66. |
| PLEASE SEE 40AMP DISCONNECT STILL SHOWN WITH 5-#8 |
| CONDUCTORS TO A 2-POLE 40AMPS DISCONNECT IN A 3/4 INCH |
| CONDUIT. |
| PLEASE SEE NO MAIN FOR TAPPED CONDUCTORS FOR NEW PANEL |
| PER 240.21, 310.16, 240.4, 408.36 ETC |
| PLEASE SEE 700.12F FOR CIRCUITING OF EMERGENCY AND EXIT |
| LIGHTS (THIS WILL BE NOTED BELOW FOR SPACE). PLEASE SEE |
| NO PANEL SCHEDULE WAS SUBMITTED FOR HPB, YET THIS PANEL |
| IS IN THE NEW TENANT SPACE BEING CREATED. 408.4, 240.4, |
| 310.16 ETC. |
| FBC 106.3.5.1.2, 106.1.2 FOR ADDITIONAL INFORMATION. |
| |
| 5) NOTE: PLEASE SEE FBC 13-101.1, 13-415.1.ABC.1.1, |
| .1.2AS NO LIGHTING CONTROLS OR SYSTEM WAS SUBMITTED |
| FOR REVIEW. LIGHTING IS NOTED AS *ALL EXISTING* WITH |
| NEW CIRCUITS YET NO LIGHTING CONTROLS WERE SUBMITTED. |
| |
| 6) NOTE: PLEASE SEE CIRCUITING PER 700.12F FOR |
| EMERGENCY AND EXIT LIGHTS SHALL BE CIRCUITED TO THE |
| LOCAL BRANCH CIRCUIT FEEDING LOCAL LIGHTING. |
| |
| 7) NOTE: PLEASE SEE MISSING SHOW WINDOW RECEPTACLES PER |
| 210.62, 220.43 |
| THE NEW SIGN CIRCUIT WHICH IS PART OF 600.5 IS NOT THE |
| SAME. |
| |
| 8) NOTE: PLEASE SEE TWO SETS OF ENERGY CALCULATIONS |
| WERE SUBMITTED SHOWING A METHOD *A* AND METHOD *B*. |
| PLEASE SEE THAT METHOD *A* CAN NOT BE USED AS THIS IS |
| NOT A *WHOLE BUILDING*. |
| PLEASE SEE 13-415.2 AS THIS IS ALREADY A CONDITIONED |
| SPACE AND RE-FEEDING THE EXISTING UNIT. |
| PLEASE SEE THE ENERGY CALCULATIONS AS SUBMITTED DO NOT |
| CONTAIN ANY INPUT DATA REPORTS AS REQUIRED. PLEASE SEE |
| PAGE #2 WHICH SPECIFICALLY MENTIONS THAT THE |
| CALCULATION SUMMARY SHEETS MUST BE ACCOMPANIED BY THE |
| INPUT DATA REPORT. |
| PLEASE SEE THE JURISTICTION IS LISTED AS PALM BEACH |
| COUNTY. |
| WE ARE UNABLE TO REVIEW FOR CODE COMPLIANCE AT THIS |
| TIME. |
| PLEASE BE SURE TO COMPLETE FIXTURE LEGEND FOR |
| FIXTURES. |
| |
| 9) NOTE: PLEASE PROVIDE NEW ROOF-TOP GFI PER 210.63, |
| 210.8. |
| AS THIS IS A NEW TENANT, ANY EXISTING DEVICES WOULD |
| NOT BE FED FROM OTHER POWER SOURCE LOCATIONS. |
| |
| 10) NOTE: PLEASE VERIFY PANEL AS SHOWN AS 200AMPS IS |
| 200AMPS. THIS IS MOST LIKELY A 225AMP AND WILL CONTAIN |
| A 200AMP MCB. |
| PANEL MENTIONS *FUSED AT DISCONNECT* HOWEVER AS NO |
| DISCONNECT IS SHOWN ON RISER THIS IS NOT POSSIBLE. |
| PLEASE VERIFY AND ADJUST AS NOTED ABOVE FOR TAPPED |
| CONDUCTORS. |
| 240.21, 310.16, 90.7, 110.3 ETC |
| FBC 106.3.5.1.2, 106.1.2 FOR ADDITIONAL INFORMATION. |
| |
| 11) NOTE: PLEASE SEE NO RESPONSE WAS PROVIDED ON |
| WHETHER OR NOT THE BUILDING CONTAINS A FIRE ALARM |
| SYSTEM? |
| PLEASE SEE THE MECHANICAL PLANS INDICATE A NEW HORN |
| STROBE FOR UNIT AND AS THIS IS NOT SHOWN ON ELECTRICAL |
| IT IS BEING *ASSUMED* THIS IS LOCATED IN SPACE. PLEASE |
| KNOW IF ANY FA SYSTEM IS LOCATED OR WILL BE MODIFIED, |
| ALL DEVICES SHALL COMPLY WITH FBC 11-4.28.1,.2 AND |
| .3(4). |
| |
| 12) NOTE: PLEASE SEE WALL WHICH CONTAINS RECEPTACLES |
| WHICH MENTIONS TO PROVIDE EXTENSIONS, HOWEVER NO |
| CIRCUITING ON HOW THESE ARE FED IS SHOWN. |
| PLEASE ALSO COORDINATE SHEET M-1, E-2 AS THE ELECTRICAL |
| SHEETS E-1 ONLY CONTAINS TWO ELECTRICAL PANELS AND E-2 |
| CONTAINS 3. |
| FBC 106.1.2, ADDITIONAL INFORMATION/COORDINATION. |
| |
| 13) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| REPEAT COMMENTS FOR CODE COMPLIANCE. |
| |
| ** PLEASE KNOW THAT A FIELD INSPECTION MAY BE NEEDED TO |
| GO OVER EXISTING WORK AND PROPOSED NEW. |
| |
| ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |