Plan Review Notes For Permit 07100119 |
Permit Number |
07100119 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2007-11-17 12:30:00 | DENIED; | | 1. PLANS ARE REQUIRED TO BE OF SUFFICIENT CLARITY WITH | | NO HAND WRITEN COMMENTS. SEE FBC CHAPTER | | 1ADMINISTRATION AMENDMENTS, SECTION 106.1.1. | | 2. ONE TOILET ROOM IS ONLY 4'- 10" NOT WIDE ENOUGH FOR | | A 5' TURNING RADIUS. REQUIRED BY FBC BUILDING CHAPTER | | 11. | | 3.THE SANITARY RISER DIAGRAM DOES NOT MATCH THE FLOOR | | PLAN. (SECOND REQUEST). SANITARYRISER DIAGRAM SHOWS | | ONLY 1 W/C AND 1 LAV. A FLOOR DRAIN IS SHOWN ON THE | | RISER DIAGRAM BUT NOT ON THE FLOOR PLANS, AND BREAK | | SINK REQUIRES A VENT. NOT SHOWN. | | 4. WATER RISER DIAGRAM; MAIN SHUTOFF VALVE REQUIRED, | | NOT SHOWN. | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 |
|