2007-11-17 12:30:00DENIED;
 1. PLANS ARE REQUIRED TO BE OF SUFFICIENT CLARITY WITH
 NO HAND WRITEN COMMENTS. SEE FBC CHAPTER
 1ADMINISTRATION AMENDMENTS, SECTION 106.1.1.
 2. ONE TOILET ROOM IS ONLY 4'- 10" NOT WIDE ENOUGH FOR
 A 5' TURNING RADIUS. REQUIRED BY FBC BUILDING CHAPTER
 11.
 3.THE SANITARY RISER DIAGRAM DOES NOT MATCH THE FLOOR
 PLAN. (SECOND REQUEST). SANITARYRISER DIAGRAM SHOWS
 ONLY 1 W/C AND 1 LAV. A FLOOR DRAIN IS SHOWN ON THE
 RISER DIAGRAM BUT NOT ON THE FLOOR PLANS, AND BREAK
 SINK REQUIRES A VENT. NOT SHOWN.
 4. WATER RISER DIAGRAM; MAIN SHUTOFF VALVE REQUIRED,
 NOT SHOWN.