Plan Review Notes For Permit 07100119 |
Permit Number |
07100119 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-10-23 13:41:11 | ***DENIED*** | | | | 1) PLEASE SEE ADDRESSING COMMENT. IF SEPARATE UNIT | | NUMBERS ARE BEING USED, SHOW ON PLANS WHERE CHARACTERS | | ARE TO BE A MINIMUM OF 3" IN HEIGHT AND CONTRASTING TO | | BACKGROUND. THE MAIN ADDRESS FOR THE BUILDING SHALL BE | | A MINIMUM OF 6" IN HEIGHT. | | | | 2) CLEARLY IDENTIFY EXIT SIGNS AND EMERGENCY LIGHTING | | FACILITIES. | | | | 3) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR FIRE | | SPRINKLER AND FIRE ALARM REMODEL. | | | | 4) IF BUILDING HAS A FIRE ALARM SYSTEM, DUCT SMOKE | | DETECTORS SHALL BE WIRED TO SYSTEM, AND INITIATE A | | GENERAL FIRE ALARM IN ACCORDANCE WITH LOCAL | | REQUIREMENTS. | | | | 5) LIFE SAFETY TO COMPLY WITH NFPA 101, 2003 EDITION. | | | | 6) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY | | WITH NFPA 241. | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | FIRE PLAN REVIEW | | FIRE PREVENTION (561) 804-4756 |
|