2007-10-14 11:57:01 | ** DENIED ** |
| |
| 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH |
| ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS |
| UNDER THE NEW CODES ADOPTED BY THE STATE. |
| PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| AFFECT DESIGNS FOR ALL TRADES. |
| PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| REVIEWER AT A MINIMUM. |
| 2004 FBC W/ 2006 REVISIONS |
| 2005 NFPA-70 |
| 2002 NFPA-72 |
| 2003 NFPA-101 |
| |
| ** PLEASE KNOW THAT CHANGES FOR NEW CODES IS REQUIRED |
| FOR ALL TRADES AND FOR ALL REVIEWS EVEN IF COMMENT IS |
| NOT MADE BY OTHER TRADE(S). |
| |
| |
| 2) NOTE: PLEASE SEE MISSING PRINTED LICENSE NUMBER FOR |
| DESIGN PROFESSIONAL AS REQUIRED PER FAC 61G15-23.002. |
| |
| 3) NOTE: PLEASE SUBMIT A CODE COMPLIANT RISER FOR |
| EXISTING AND NEW. PLEASE SEE THERE ARE SEVERAL ITEMS |
| WHICH ARE NOT CORRECT. |
| FOR EXAMPLE: CONDUCTOR SIZES ON FEEDERS WHICH ARE SHOWN |
| AS 5/0'S AT SEVERAL LOCATIONS WHICH IS NOT POSSIBLE AS |
| THERE ARE NO 5/0 CONDUCTORS BASED ON AWG (AMERICAN WIRE |
| GAUGE). PLEASE SEE 240.4 AND 310.16 AND ADJUST ALL NEW |
| AND EXISTING CONDUCTORS ON RISER FOR CODE COMPLIANCE. |
| PLEASE SEE 700.12F FOR CIRCUITING OF EMERGENCY AND EXIT |
| LIGHTS. |
| PLEASE LABEL AND CORRELATE PANELS AND EQUIPMENT ON |
| RISER. (HPE, MAIN ETC) |
| PLEASE COMPLETE RISER FOR EXISTING AND NEW.215.5, 230, |
| 240.4, 310.16 ETC |
| |
| 4) NOTE: PLEASE COMPLETE CIRCUITING ON PLANS FOR NEW. |
| FBC 106.1.2, 106.3.5.1.2 |
| NEC 408.4 AS CIRCUITS NEED TO BE SPECIFIC TO ROOMS AND |
| AREAS IN WHICH THEY FEED. |
| PLEASE SEE 700.12F AS NOTED ABOVE FOR EM/EXT LTS. |
| |
| 5) NOTE: PLEASE SEE 210.62 AND 220.43 FOR MISSING STORE |
| FRONT WINDOW RECEPTACLES REQUIRED WHICH ARE NOT SHOWN |
| AT THIS TIME. |
| |
| 6) NOTE: PLEASE SEE 600.5 FOR SIGN CIRCUIT. IS THE ONE |
| SHOWN ON EXISTING PANEL *MAIN* THE SAME AS HPE? PLEASE |
| CORRELATE. |
| |
| 7) NOTE: PLEASE SEE PANEL MAIN, INDICATES A 90AMP |
| BREAKER ON #8AWG WHICH IS NOT SUFFICIENT. |
| PLEASE COORDINATE AND COMPLETE. |
| |
| 8) NOTE: PLEASE KNOW ONCE THE ADDRESSING REVIEW IS |
| COMPLETED, A NEW SUITE/UNIT WILL BE GIVEN AND THIS |
| NEEDS TO BE STATED ON PLANS. |
| THE SCOPE WORK ON TITLE BLOCK MENTIONS NEW RETAIL |
| STORE, YET PLANS CALL FOR SPACE TO BE PART OF FUTURE |
| BUILD OUT? |
| PLEASE CLARIFY IF THIS IS TWO NEW SPACES BEING CREATED |
| FROM THE EXISTING STORE. |
| FBC 106.1.2, 110.1.2. |
| FAC 61G15-23.002 |
| |
| 9) NOTE: PLEASE CLARIFY IF THIS EXISTING BUILDING/SPACE |
| HAS A FIRE ALARM SYSTEM. IF YES, PLEASE INDICATE THE |
| LOCATIONS AND DEVICE LEVELS FOR ADA COMPLIANCE PER FBC |
| 11-4.28.1,.2 AND .3(4). |
| **(EVEN AS FA WOULD BE UNDER SEPARATE PERMITS) |
| ** (THIS IS ONLY NOTED AND THIS REVIEWER IS NOT STATING |
| THAT A FA SYSTEM IS REQUIRED. (ONLY REVIEWING FOR ADA |
| COMPLIANCE IF SYSTEM EXISTS OR WILL BE REQUIRED PER |
| BUILDING REVIEWER OR FIRE MARSHAL) |
| |
| ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES |
| WHICH MAY AFFECT ELECTRICAL PLANS. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |