Notes
Date Text
2007-10-14 11:57:01** DENIED **
  
 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 ** PLEASE KNOW THAT CHANGES FOR NEW CODES IS REQUIRED
 FOR ALL TRADES AND FOR ALL REVIEWS EVEN IF COMMENT IS
 NOT MADE BY OTHER TRADE(S).
  
  
 2) NOTE: PLEASE SEE MISSING PRINTED LICENSE NUMBER FOR
 DESIGN PROFESSIONAL AS REQUIRED PER FAC 61G15-23.002.
  
 3) NOTE: PLEASE SUBMIT A CODE COMPLIANT RISER FOR
 EXISTING AND NEW. PLEASE SEE THERE ARE SEVERAL ITEMS
 WHICH ARE NOT CORRECT.
 FOR EXAMPLE: CONDUCTOR SIZES ON FEEDERS WHICH ARE SHOWN
 AS 5/0'S AT SEVERAL LOCATIONS WHICH IS NOT POSSIBLE AS
 THERE ARE NO 5/0 CONDUCTORS BASED ON AWG (AMERICAN WIRE
 GAUGE). PLEASE SEE 240.4 AND 310.16 AND ADJUST ALL NEW
 AND EXISTING CONDUCTORS ON RISER FOR CODE COMPLIANCE.
 PLEASE SEE 700.12F FOR CIRCUITING OF EMERGENCY AND EXIT
 LIGHTS.
 PLEASE LABEL AND CORRELATE PANELS AND EQUIPMENT ON
 RISER. (HPE, MAIN ETC)
 PLEASE COMPLETE RISER FOR EXISTING AND NEW.215.5, 230,
 240.4, 310.16 ETC
  
 4) NOTE: PLEASE COMPLETE CIRCUITING ON PLANS FOR NEW.
 FBC 106.1.2, 106.3.5.1.2
 NEC 408.4 AS CIRCUITS NEED TO BE SPECIFIC TO ROOMS AND
 AREAS IN WHICH THEY FEED.
 PLEASE SEE 700.12F AS NOTED ABOVE FOR EM/EXT LTS.
  
 5) NOTE: PLEASE SEE 210.62 AND 220.43 FOR MISSING STORE
 FRONT WINDOW RECEPTACLES REQUIRED WHICH ARE NOT SHOWN
 AT THIS TIME.
  
 6) NOTE: PLEASE SEE 600.5 FOR SIGN CIRCUIT. IS THE ONE
 SHOWN ON EXISTING PANEL *MAIN* THE SAME AS HPE? PLEASE
 CORRELATE.
  
 7) NOTE: PLEASE SEE PANEL MAIN, INDICATES A 90AMP
 BREAKER ON #8AWG WHICH IS NOT SUFFICIENT.
 PLEASE COORDINATE AND COMPLETE.
  
 8) NOTE: PLEASE KNOW ONCE THE ADDRESSING REVIEW IS
 COMPLETED, A NEW SUITE/UNIT WILL BE GIVEN AND THIS
 NEEDS TO BE STATED ON PLANS.
 THE SCOPE WORK ON TITLE BLOCK MENTIONS NEW RETAIL
 STORE, YET PLANS CALL FOR SPACE TO BE PART OF FUTURE
 BUILD OUT?
 PLEASE CLARIFY IF THIS IS TWO NEW SPACES BEING CREATED
 FROM THE EXISTING STORE.
 FBC 106.1.2, 110.1.2.
 FAC 61G15-23.002
  
 9) NOTE: PLEASE CLARIFY IF THIS EXISTING BUILDING/SPACE
 HAS A FIRE ALARM SYSTEM. IF YES, PLEASE INDICATE THE
 LOCATIONS AND DEVICE LEVELS FOR ADA COMPLIANCE PER FBC
 11-4.28.1,.2 AND .3(4).
 **(EVEN AS FA WOULD BE UNDER SEPARATE PERMITS)
 ** (THIS IS ONLY NOTED AND THIS REVIEWER IS NOT STATING
 THAT A FA SYSTEM IS REQUIRED. (ONLY REVIEWING FOR ADA
 COMPLIANCE IF SYSTEM EXISTS OR WILL BE REQUIRED PER
 BUILDING REVIEWER OR FIRE MARSHAL)
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717