Plan Review Notes For Permit 07100095 |
Permit Number |
07100095 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-10-17 14:17:43 | 1. THE ENTIRE FIRE ALARM SYSTEM INSTALLATION TO COMPLY | | WITH NFPA 72, THE NATIONAL FIRE ALARM CODE. | | | | 2. AS PER THE ATTACHED LETTER, DUCT SMOKE DETECTORS | | WHEN ACTIVATED SHALL CAUSE FIRE ALARM ACTIVATION NOT A | | SUPERVISORY SIGNAL. | | | | 3. A REVISION WILL BE NECESSARY TO CHANGE THE SMOKE | | DETECTOR LOCATED WITHIN THE LOBBY TO THE DESIRED HEAT | | DETECTOR. | | | | 4. AFTER INSTALLATION, THE ENTIRE SYSTEM SHALL BE | | INSPECTED, TESTED, AND APPROVED BY THIS DEPARTMENT. | | | | 5. SMOKE DETECTORS SHALL BE INSTALLED A MINIMUM OF AT | | LEAST THREE FEET FROM AIR CONDITIONER DIFFUSERS. | | | | APPROVED PROVISO: | | | | MIKE CARSILLO, BATTALION CHIEF | | 804-4709 PHONE | | 804-4774 FAX |
|