2008-03-17 16:45:25PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) SEE YELLOW HIGH LIGHT ON PLANS SHOWING TWO SUPPLY
 AIR DUCTS THAT NEED TO BE SIZED, PER 2004 FBC 106.3.5.
  
 2) PLEASE ADD AN A/C EQUIPMENT SCHEDULE TO THE PLAN AS
 THE ORIGINAL PERMIT APPLICATION WAS FOR A 1.0 TON A/C
 UNIT, SEE ATTACHED COPY OF APPLICATION.
  
 3) PLEASE SHOW THE CFM'S AT ALL SUPPLY AIR GRILLS.
  
 4) SHOW ON PLAN HOW THE AIR IS RETURNING TO THE UNIT,
 IF EXISTING PLEASE STATE SO ON PLAN.
  
 5) ADD OUT-SIDE AIR CALCULATIONS TO PLAN, PER 2004
 FBC/M 403.2.
  
 6) AS THE SCOPE OF WORK HAS CHANGED PLEASE ADJUST THE
 VALUE TO THE PERMIT TO SHOW ALL THE EXTRA WORK BEING
 DONE, PLEASE BE AWARE IF THE VALUE IS NOT THE
 REPLACEMENT VALUE FOR ALL THE LABOR AND MATERIALS THE
 CITY WILL NEED TO ADJUST IT, PER 2004 W./P.B AMEND.
 108.3.
  
 7) A NOTICE OF COMMENCEMENT WILL NEED TO BE FILED DUE
 TO THE INCREASE IN VALUE, PER F. S. 713.13 .
  