2008-03-17 16:45:25 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | (F.S.). | | | | *** DENIED *** | | 1) SEE YELLOW HIGH LIGHT ON PLANS SHOWING TWO SUPPLY | | AIR DUCTS THAT NEED TO BE SIZED, PER 2004 FBC 106.3.5. | | | | 2) PLEASE ADD AN A/C EQUIPMENT SCHEDULE TO THE PLAN AS | | THE ORIGINAL PERMIT APPLICATION WAS FOR A 1.0 TON A/C | | UNIT, SEE ATTACHED COPY OF APPLICATION. | | | | 3) PLEASE SHOW THE CFM'S AT ALL SUPPLY AIR GRILLS. | | | | 4) SHOW ON PLAN HOW THE AIR IS RETURNING TO THE UNIT, | | IF EXISTING PLEASE STATE SO ON PLAN. | | | | 5) ADD OUT-SIDE AIR CALCULATIONS TO PLAN, PER 2004 | | FBC/M 403.2. | | | | 6) AS THE SCOPE OF WORK HAS CHANGED PLEASE ADJUST THE | | VALUE TO THE PERMIT TO SHOW ALL THE EXTRA WORK BEING | | DONE, PLEASE BE AWARE IF THE VALUE IS NOT THE | | REPLACEMENT VALUE FOR ALL THE LABOR AND MATERIALS THE | | CITY WILL NEED TO ADJUST IT, PER 2004 W./P.B AMEND. | | 108.3. | | | | 7) A NOTICE OF COMMENCEMENT WILL NEED TO BE FILED DUE | | TO THE INCREASE IN VALUE, PER F. S. 713.13 . | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|