2007-10-25 09:24:26PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLEASE SUBMIT DETAILED MANUFACTURER'S INSTALLATION
 INSTRUCTIONS SHOWING REQUIRED CLEARANCES FOR GENERATOR,
 SEE NFPA 37 (4.1.4).
  
 2) PLEASE STATE WHAT THE BUILDING IS MADE OF AND IF
 COMBUSTIBLE, SEE NFPA 37 (4.1.4).
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729