Date |
Text |
2007-10-26 08:53:29 | DENIED |
| REFERENCE: |
| ** FBC-2004 WITH 05 & 06 REVISIONS, FUEL GAS. |
| ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION |
| REQUIREMENTS. |
| ** FBC-2004 CHAPTER 1, THE CITY OF |
| WEST PALM BEACH AMENDMENTS. |
| ** FLORIDA ADMINISTRATIVE CODE (FAC). |
| ** FLORIDA STATUTES (FS). |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| GAS PLAN REVIEW TO MEET CODE COMPLIANCE: |
| **CONTRACTOR INFORMATION: THE SUBMITTED GAS PERMIT |
| REFERENCED MASTER PERMIT #06060974, THAT PERMIT NUMBER |
| IS EXPIRED. THE CORRECT MASTER PERMITNUMBER IS |
| #07100077. PLEASE NOTE THE RED LINE CORRECTIONS ON THE |
| PERMIT APPLICATION. |
| |
| 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE. |
| **NOTE: THE SUBMITTED ISOMETRIC DRAWING MUST INDICATE |
| THE CORRESPONDING LENGTHS OF THE CUT SECTIONS OF PIPE |
| TO VERIFY THE GIVEN DEVELOPED LENGTH OF 20' ON THE |
| RESUBMITTAL. |
| |
| 2. PLEASE CORRELATE THE GENERATOR SIZE AND BTU LOAD ON |
| THE RESUBMITTED DRAWINGS WITH THE MASTER GEN/RES PERMIT |
| #07100077. THE MASTER GEN/RES PERMIT INDICATES A 35 KW, |
| 560,000 BTU GENERATOR. THE SUBMITTED GAS ISOMETRIC IS |
| INDICATING A 40 KW, 650,000 BTU GENERATOR. PER *106.1.1 |
| INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| 3. PER FBC-2004 FUEL GAS SECTION 409.5 EQUIPMENT |
| SHUTOFF VALVE: EACH APPLIANCE SHALL BE PROVIDED WITH A |
| SHUTOFF VALVE SEPERATE FROM THE APPLIANCE. THE SHUTOFF |
| VALVE SHALL BE LOCATED IN THE SAME ROOM AS THE |
| APPLIANCE, NOT FURTHER THAN 6 FEET FROM THE APPLIANCE, |
| AND SHALL BE INSTALLED UPSTREAM FROM THE UNION, |
| CONNECTOR OR QUICK DISCONNECT DEVICE IT SERVES. SUCH |
| SHUTOFF VALVES SHALL BE PROVIDED WITH ACCESS. |
| |
| END OF COMMENTS: |
| |
| REVIEW BY: MIKE PERSON |
| PLUMBING PLANS EXAMINER |
| (561) 805-6730 |
| FAX (561) 805-6731 |
| E-MAIL: [email protected] |
| |