Plan Review Notes
Plan Review Notes For Permit 07100072
Permit Number 07100072
Review Stop G
Sequence Number 1
Notes
Date Text
2007-10-16 14:38:12DENIED
 REFERENCE:
 ** FBC-2004 WITH 05 & 06 REVISIONS, FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE (FAC).
 ** FLORIDA STATUTES (FS).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS/PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 NOTE: PLEASE INDICATE THE CORRESPONDING LENGTHS TO ALL
 CUT SECTIONS OF PIPE ON THE RESUBMITTAL AND INDICATE
 THE LOCATION OF THE EXISTING POOL HEATER. SEE ATTACHED
 PERMIT INFORMATION TO THE GAS COMMENTS INDICATING GAS
 TO AN EXISTING POOL HEATER.
  
 2. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 NOTE: PERMIT INFORMATION INDICATES EXISTING GAS TO A
 POOL HEATER, THE BTU LOAD FOR THE EXISTING SYSTEM NEEDS
 TO BE ON THE RESUBMITTAL.
  
 3. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 NOTE: LONGEST LENGTH OF THE SYSTEM NEEDS TO BE
 INDICATED ON THE PLANS, THIS INCLUDES THE POOL HEATER.
 IF GAS PIPING TO THE EXISTING POOL HEATER IS LONGER
 THAN THE PROPOSED ADDITION GAS OF 25 FEET GAS SYSTEM
 WILL NEED TO BE RESIZED.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731