2007-11-02 09:02:04 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST |
| PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA |
| ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES |
| (F.S.). |
| |
| *** DENIED *** |
| 1) SHOW ON PLAN HOW THE OUTDOOR AIR IS GOING TO GET IN |
| THE BUILDING, PER 2004 FBC/M 401.2. |
| |
| 2) AS NOTED IN LAST REVIEW 10-18-07 NOTE #7 PLEASE |
| SUBMIT PRODUCT APPROVAL OR AN NOA FOR PER-ENGINEERED |
| CONDENSER STANDS, SEE FS 553.842(1) AND FAC RULE 9B-72, |
| 9B-72.005, AND FAC 9B-72.010(31)(G). WHAT WAS SUBMITTED |
| WAS ENGINEERING SHEETS NOT PRODUCT APPROVALS. |
| |
| **PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION |
| AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE |
| FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE |
| SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. |
| PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT |
| IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT |
| HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR |
| LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE |
| 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG. |
| |