Plan Review Notes
Plan Review Notes For Permit 07100065
Permit Number 07100065
Review Stop M
Sequence Number 1
Notes
Date Text
2007-10-18 09:55:18PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLEASE SUBMITCOOLING LOAD CALCULATIONS, PER 2004
 FBC 13-407.1.ABC.1.
  
 2) PLEASE SUBMIT OUTDOOR AIR CALCULATIONS AND PROVIDE
 OUTDOOR AIR, SEE 2004 FBC/M 401.2.
  
 3) NEED TO SHOW THE SUPPLY AIR CFM'S AT THE GRILLS, SEE
 FBC 13-410.1.ABC.4.2.
  
 4) NEED TO PROVIDE FOR RETURN AIR TO OFFICE, SEE FBC/M
 601.4.
  
 5) THE MECHANICAL PLANS NEED THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN ON
 THEM, SEE W.P.B. AMEND. 106.1.3.
  
 6) PLEASE ADJUST VALUE ON PERMIT APPLICATION TO SHOW
 FAIR MARKET VALUE OR THE CITY WILL ADJUST VALUE USING
 MARSHALL AND SWIFT SEGREGATED COST METHOD, SEE W.P.B.
 108.3.
  
 7) PLEASE SUBMIT PRODUCT APPROVAL OR AN NOA FOR
 PER-ENGINEERED CONDENSER STANDS, SEE FS 553.842(1) AND
 FAC RULE 9B-72, 9B-72.005, AND FAC 9B-72.010(31)(G).
  
 **PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]