2007-10-18 09:55:18 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST |
| PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA |
| ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES |
| (F.S.). |
| |
| *** DENIED *** |
| 1) PLEASE SUBMITCOOLING LOAD CALCULATIONS, PER 2004 |
| FBC 13-407.1.ABC.1. |
| |
| 2) PLEASE SUBMIT OUTDOOR AIR CALCULATIONS AND PROVIDE |
| OUTDOOR AIR, SEE 2004 FBC/M 401.2. |
| |
| 3) NEED TO SHOW THE SUPPLY AIR CFM'S AT THE GRILLS, SEE |
| FBC 13-410.1.ABC.4.2. |
| |
| 4) NEED TO PROVIDE FOR RETURN AIR TO OFFICE, SEE FBC/M |
| 601.4. |
| |
| 5) THE MECHANICAL PLANS NEED THE PRINTED NAME AND |
| SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN ON |
| THEM, SEE W.P.B. AMEND. 106.1.3. |
| |
| 6) PLEASE ADJUST VALUE ON PERMIT APPLICATION TO SHOW |
| FAIR MARKET VALUE OR THE CITY WILL ADJUST VALUE USING |
| MARSHALL AND SWIFT SEGREGATED COST METHOD, SEE W.P.B. |
| 108.3. |
| |
| 7) PLEASE SUBMIT PRODUCT APPROVAL OR AN NOA FOR |
| PER-ENGINEERED CONDENSER STANDS, SEE FS 553.842(1) AND |
| FAC RULE 9B-72, 9B-72.005, AND FAC 9B-72.010(31)(G). |
| |
| **PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION |
| AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE |
| FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE |
| SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. |
| PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT |
| IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT |
| HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR |
| LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE |
| 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG. |
| |