Plan Review Notes
Plan Review Notes For Permit 07100060
Permit Number 07100060
Review Stop B
Sequence Number 2
Notes
Date Text
2007-11-19 10:30:25****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 COMMENTS FROM PREVIOUS LISTS:
  
 1.)YOU CANNOT APPLY FOR OWNER BUILDER PERMITS FOR
 COMMERCIAL PROPERTIES.
  
 PLEASE READ FLORIDA STATUTE 489, "THE BUILDING OR
 RESIDENCE MUST BE FOR YOUR OWN USE OR OCCUPANCY.IT
 MAY NOT BE BUILT OR SUBSTANTIALLY IMPROVED FOR SALE OR
 LEASE."MIGUEL LAVIN IS THE OWNER, EL LATINO AND
 MIGUEL LAVIN BARBER SHOP ARE THE TENANTS.OWNER
 BUILDER NOT ALLOWED FOR CORPORATIONS AS PER STATE OF
 FLORIDA AND BUILDING OFFICIAL.THIS BUILDING IS RENTED
 OR LEASED, HAS TWO TENANTS WHICH ARE CORPORATIONS.
 OWNERSHIP OF THE COMPANIES WHICH LEASE OR RENT THE
 SPACES IS NOT ADDRESSED IN THE OWNER BUILDER LAW.
  
 2.)THE RAMP WHICH WAS REMOVED MUST BE REPLACED.SEE
 FBC11-4.1.6(1)(B), NO ALTERATION SHALL BE UNDERTAKEN
 WHICH DECREASES OR HAS THE EFFECT OF DECREASING
 ACCESSIBILITY OR USABILITY OF A BUILDING OR FACILITY
 BELOW THE REQUIREMENTS FOR NEW CONSTRUCTION AT THE TIME
 OF ALTERATION.REVISE THE PLAN TO INCLUDE A RAMP OR
 PROVIDE OTHER MEANS OF VERTICAL ACCESSIBILITY (ELEVATOR
 OR LIFT).
  
 3.)ALTERATIONS TO EXISTING BUILDINGS SHALL COMPLY
 WITH THE FOLLOWING; IF EXISTING ELEMENTS, SPACES, OR
 COMMON AREAS ARE ALTERED, THEN EACH SUCH ALTERED
 ELEMENT, SPACE, FEATURE, OR AREA SHALL COMPLY WITH THE
 APPLICABLE PROVISIONS OF SECTION 11-4.1.1 TO SECTION
 11-4.1.3, MINIMUM REQUIREMENTS FOR NEW CONSTRUCTION,
 FBC11-4.1.6.SEE ALSO ITEM #2.REVISE PLAN TO PROVIDE
 VERTICAL ACCESSIBILITY.
  
 4.)THE GUARD IS TO COMPLY WITH FBC1012.THE HEIGHT
 SPECIFIED IN THE NOTES (42 INCHES) AND "RAILING BLOW
 UP" CONFLICTS WITH OTHER DETAILS ON THE PLAN, SUCH AS
 NORTH ELEVATION, WHICH SPECIFY 2'10".
  
 5.)IT DOES NOT APPEAR THE THE 1X2 PICKETS COMPLY WITH
 THE DESIGN STRENGTH REQUIREMENTS OF FBC1607.PROVIDE
 CALCULATIONS.
  
 6.)SHOW THE DISTANCE BETWEEN THE TOP OF THE PICKETS
 AND THE RAILING.FBC1012.3.SHOW DIMENSIONS AT
 OPENINGS AT THE BOTTOM OF THE PICKETS.
  
 7.)HANDRAIL EXTENSIONS AT THE BOTTOM DO NOT COMPLY
 WITH FBC11-4.9.4(2).
  
 8.)FOR THE RAILING WHICH IS NOT AGAINST THE WALL,
 SHOW THE EXTENSION DIMENSIONS (THE SLOPED PORTION, THE
 PORTION PARALLEL TO THE GROUND).FBC11-4.9.4(2).
  
 9.)SHOW COMPLIANCE WITH FBC11-4.9.4(6).PROVIDE A
 DETAIL FOR THE WALL MOUNTED RAIL AND A DETAIL FOR THE
 HANDRAIL AT THE GUARD.AS DRAWN, THE HANDRAIL
 EXTENSIONS ARE A HAZARD.
  
 10.)SEE ATTACHED FS553.80(2)(B).A FEE WILL BE
 CHARGED IF THE PLAN REVIEW COMMENTS ARE NOT ADDRESSED A
 THIRD TIME AND MAY BE CHARGED ON PAST PLAN REVIEWS AS
 THIS IS REQUIRED BY FLORIDA STATUTE.
  
 A SET HAS BEEN RETAINED.
  
  
  
  
  
  
  
  