Plan Review Notes
Plan Review Notes For Permit 07100053
Permit Number 07100053
Review Stop E
Sequence Number 1
Notes
Date Text
2007-10-10 07:55:49 
  
 APPLICATION # 07100053
 ELECTRICAL PLAN REVIEW
 519 41ST STREET
 10/10/07
 WEST PALM BEACH, FL.
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} PROVIDE LOAD CALCULATIONS PER ARTICLE 220 PART III,
 STANDARD OR PART IV OPTIONAL, INDICATE METHOD USED,
 INCLUDE THE ADDED A/C SYSTEM AND INDICATE THE RATING OF
 THE EXISTING SERVICE. THIS IS TO DETERMINE IF THE
 SERVICE IS ADEQUATE FOR THE ADDED LOAD.
  
 2} PLANS INDICATING THE SCOPE OF WORK MUST BE SUBMITTED
 WITH THE APPLICATION PER 106.1 FBC AS AMENDED. SHOW THE
 LOCATION OF THE A/C EQUIPMENT ON THE PLAN. ALSO SHOW
 COMPLIANCE WITH THE REQUIRED DISCONNECT PER 440.14,
 RECEPTACLE PER 210.63, LIGHT PER 210.70(A) (3). THE
 FLOOR PLAN SHALL ALSO INDICATE THE LOCATION OF ALL
 ELECTRICAL WORK UNDER THE SCOPE OF THIS APPLICATION.
  
 3} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHEN INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS
 REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING
 ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE
 INDIVIDUAL DWELLING UNIT SHALL BE PROVIDED WITH SMOKE
 ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE
 ALARMS SHALL BE INTERCONNECTED AND HARD WIRED. LOCATE
 SAME ON THE PLANS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER