2007-10-10 07:55:49 | |
| |
| APPLICATION # 07100053 |
| ELECTRICAL PLAN REVIEW |
| 519 41ST STREET |
| 10/10/07 |
| WEST PALM BEACH, FL. |
| |
| THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| |
| THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 |
| RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, |
| NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND |
| FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| |
| 1} PROVIDE LOAD CALCULATIONS PER ARTICLE 220 PART III, |
| STANDARD OR PART IV OPTIONAL, INDICATE METHOD USED, |
| INCLUDE THE ADDED A/C SYSTEM AND INDICATE THE RATING OF |
| THE EXISTING SERVICE. THIS IS TO DETERMINE IF THE |
| SERVICE IS ADEQUATE FOR THE ADDED LOAD. |
| |
| 2} PLANS INDICATING THE SCOPE OF WORK MUST BE SUBMITTED |
| WITH THE APPLICATION PER 106.1 FBC AS AMENDED. SHOW THE |
| LOCATION OF THE A/C EQUIPMENT ON THE PLAN. ALSO SHOW |
| COMPLIANCE WITH THE REQUIRED DISCONNECT PER 440.14, |
| RECEPTACLE PER 210.63, LIGHT PER 210.70(A) (3). THE |
| FLOOR PLAN SHALL ALSO INDICATE THE LOCATION OF ALL |
| ELECTRICAL WORK UNDER THE SCOPE OF THIS APPLICATION. |
| |
| 3} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS. |
| WHEN INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS |
| REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING |
| ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE |
| INDIVIDUAL DWELLING UNIT SHALL BE PROVIDED WITH SMOKE |
| ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE |
| ALARMS SHALL BE INTERCONNECTED AND HARD WIRED. LOCATE |
| SAME ON THE PLANS. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |
| BILL TROBAUGH |
| ELECTRICAL PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| 561/805-6718 |