2008-02-26 11:04:45REVIEW #: REV.4
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. FIRE/SMOKE DAMPERS ARE SHOWN WHERE DUCTS PENETRATE A
 1-HOUR RATED WALL ASSEMBLY. IT IS NOT CLEAR WHY
 FIRE/SMOKE DAMPERS ARE SHOWN AT THIS LOCATON AS THIS IS
 NOT A SMOKE BARRIER. IN FACT, IT IS NOT CLEAR WHY THIS
 WALL IS RATED AT ALL. THE STORAGE ROOMS MEET THE
 CRITERIA FOR ACCESSORY USE AREAS IN ACCORDANCE WITH
 FBCB 302.2 AND THEREFORE NO RATED SEPARATION IS
 REQUIRED. THE DESIGNER CAN DESIGN ABOVE WHAT THE CODE
 REQUIRES. HOWEVER, FIRE/SMOKE DAMPERS, WHETHER REQUIRED
 OR NOT SHALL BE INSTALLED PER THEIR LISTING,
 MANUFACTURER'S INSTALLATION INSTRUCTIONS AND FBCM
 SECTION 607 IN ACCORDANCE WITH FBCM 607.2.
  
 2. PLANS DO NOT INDICATE HOW THE SMOKE DAMPERS ARE TO
 BE CONTROLLED. SMOKE DAMPERS SHALL BE CONTROLLED BY ONE
 OR A COMBINATION OF METHODS IN ACCORDANCE WITH FBCM
 607.3.2.1. IF SMOKE DAMPERS ARE TO REMAIN, SHOW
 COMPLIANCE WITH THIS SECTION.
  
 NOTE: ANY CHANGES TO THE MECHANICAL PLANS RELATED TO
 THE LOCATION OF OR THE NEED FOR DAMPERS AT DUCT
 PENETRATIONS OF THE STORAGE ROOM WALLS SHOULD BE
 COORDINATED WITH ARCHITECTURAL PLANS. ANY CHANGES TO
 ARCHITECTURAL PLANS SHALL BE SUBMITTED FOR BUILDING
 PLAN REVIEW IN CONJUNCTION WITH RESUBMITTED MECHANICAL
 PLANS.
  