2007-11-09 16:41:13REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. OK
  
 2. OK
  
 3. OK
  
 4. AH-1 IS STILL LISTED, BASED ON MODEL NUMBER, AS A
 CHILLED WATER AHU. PLAN STILL INDICATES THAT THERE IS
 AN EXISTING CONDENSING UNIT ON THE ROOF. ELECTRICAL
 PLANS STILL SHOW THERE IS ELECTRICAL SERVICE FOR A
 CONDENSING UNIT ON THE ELECTRICAL PANEL. AT LEAST ONE
 PIECE OF THIS INFORMATION IS INCORRECT. AS STATED IN
 PREVIOUS REVIEW COMMENT, THIS IS EITHER A CHILLED WATER
 SYSEM WITH NO CONDENSER (AS INDICATED BY AHU MODEL
 NUMBER) OR A SPLIT SYSTEM WITH THE WRONG AHU LISTED ON
 PLANS. PLEASE COORDINATE INFORMATION ON MECHANICAL
 PLANS REGARDING THE TYPE OF EQUIPMENT BEING USED. ALSO,
 IF IT IS DETERMINED THAT THERE IS NO CONDENSING UNIT,
 PLEASE COORDINATE WITH ELECTRICAL PLANS. SEE ATTACHED
 MANUFACTURER'S DATS FOR THE CARRIER 40RMS012 AIR
 HANDLER.
  
 5. OK
  
 6. DO THE AIR HANDLER AND EXHAUST FANS RUN CONTINUOUS?
 IF NOT, HOW WILL AIR BE PROVIDED WHENEVER THE RESTROOMS
 ARE OCCUPIED? SHOW COMPLIANCE WITH FBC,M 401.3 WHICH
 REQUIRES VENTILATION TO BE PROVIDED WHENEVER THE SPAE
 IS OCCUPIED. ALSO, OUTSIDE AIR CALCULATIONS STATE THAT
 OUTSIDE AIR FOR THE RESTROOOMS IS BEING PROVIDED VIA
 TRANSFER AIR. FLOOR PLAN SHOWS BATHROOMS PROVIDED WITH
 MECHANICAL SUPPLY AIR. WHICH IS CORRECT? SHOW
 COMPLIANCE WITH FBC,M 403.1.
  
 7. OK
  
 8. NOT FOR OUTSIDE AIR DAMPER STATES THE DAMPER IS TO
 BE CLOSED WHEN THE UNIT IS HOT IN USE. PLEASE CLARIFY.
 THIS DAMPER SHOULD REMAIN OPEN WHENEVER THE SPACE IS
 OCCUPIED AND BE CLOSED DURING UNOCCUPIED HOURS. IF THE
 AHU HAS A NIGHT MODE WHERE IT MAY BE RUNNING DURING
 UNOCCUPIED HOURS, THE DAMPER SHOULD BE CLOSED DURING
 THAT TIME IN ACCORDANCE WITH FBC 13-409.1.ABC.3.3.
  
 9. OK
  