Date |
Text |
2007-11-09 16:41:13 | REVIEW #: 2ND |
| ACTION: DENIED |
| |
| FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS |
| FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| |
| THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN |
| RESPONSES FOR THE PURPOSE OF CONTINUITY. |
| |
| 1. OK |
| |
| 2. OK |
| |
| 3. OK |
| |
| 4. AH-1 IS STILL LISTED, BASED ON MODEL NUMBER, AS A |
| CHILLED WATER AHU. PLAN STILL INDICATES THAT THERE IS |
| AN EXISTING CONDENSING UNIT ON THE ROOF. ELECTRICAL |
| PLANS STILL SHOW THERE IS ELECTRICAL SERVICE FOR A |
| CONDENSING UNIT ON THE ELECTRICAL PANEL. AT LEAST ONE |
| PIECE OF THIS INFORMATION IS INCORRECT. AS STATED IN |
| PREVIOUS REVIEW COMMENT, THIS IS EITHER A CHILLED WATER |
| SYSEM WITH NO CONDENSER (AS INDICATED BY AHU MODEL |
| NUMBER) OR A SPLIT SYSTEM WITH THE WRONG AHU LISTED ON |
| PLANS. PLEASE COORDINATE INFORMATION ON MECHANICAL |
| PLANS REGARDING THE TYPE OF EQUIPMENT BEING USED. ALSO, |
| IF IT IS DETERMINED THAT THERE IS NO CONDENSING UNIT, |
| PLEASE COORDINATE WITH ELECTRICAL PLANS. SEE ATTACHED |
| MANUFACTURER'S DATS FOR THE CARRIER 40RMS012 AIR |
| HANDLER. |
| |
| 5. OK |
| |
| 6. DO THE AIR HANDLER AND EXHAUST FANS RUN CONTINUOUS? |
| IF NOT, HOW WILL AIR BE PROVIDED WHENEVER THE RESTROOMS |
| ARE OCCUPIED? SHOW COMPLIANCE WITH FBC,M 401.3 WHICH |
| REQUIRES VENTILATION TO BE PROVIDED WHENEVER THE SPAE |
| IS OCCUPIED. ALSO, OUTSIDE AIR CALCULATIONS STATE THAT |
| OUTSIDE AIR FOR THE RESTROOOMS IS BEING PROVIDED VIA |
| TRANSFER AIR. FLOOR PLAN SHOWS BATHROOMS PROVIDED WITH |
| MECHANICAL SUPPLY AIR. WHICH IS CORRECT? SHOW |
| COMPLIANCE WITH FBC,M 403.1. |
| |
| 7. OK |
| |
| 8. NOT FOR OUTSIDE AIR DAMPER STATES THE DAMPER IS TO |
| BE CLOSED WHEN THE UNIT IS HOT IN USE. PLEASE CLARIFY. |
| THIS DAMPER SHOULD REMAIN OPEN WHENEVER THE SPACE IS |
| OCCUPIED AND BE CLOSED DURING UNOCCUPIED HOURS. IF THE |
| AHU HAS A NIGHT MODE WHERE IT MAY BE RUNNING DURING |
| UNOCCUPIED HOURS, THE DAMPER SHOULD BE CLOSED DURING |
| THAT TIME IN ACCORDANCE WITH FBC 13-409.1.ABC.3.3. |
| |
| 9. OK |
| |