Plan Review Notes For Permit 07100039 |
Permit Number |
07100039 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2007-11-09 16:16:24 | ** DENIED *** | | | | | | 1) NOTE: ELECTRICAL REVIEW STATUS HAS CHANGED TO | | FAILED. | | REVIEW CONDUCTED BY THE MECHANICAL REVIEWER INDICATES | | THE AIR CONDITIONING SYSTEMS AS CHILLED WATER, HOWEVER | | ELECTRICAL PLANS INDICATE A SPLIT SYSTEM. | | THESE PLANS WILL BE BECOME VOID AND STAMPED AS SUCH | | UNTIL COORDINATION OF ELECTRICAL PLANS AND MECHANICAL | | PLANS IS DONE. | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 |
|