Plan Review Notes
Plan Review Notes For Permit 07100039
Permit Number 07100039
Review Stop M
Sequence Number 1
Notes
Date Text
2007-10-05 14:12:58REVIEW #: 1
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PG TS: PROJECT INFORMATION, ITEM 4 INDICATES
 AIR-ZONA SYSTEMS AS THE MEP ENGINEER. HOWEVER, PG MP1.1
 IS SIGNED AND SEALED BY YV KULKARNI, PE. PLEASE CORRECT
 INFORMATION ON FRONT PAGE. AIR-ZONA SYSTEMS
 ENGINEERING, INC'S CERTIFICATE OF AUTHORIZATION IS
 LISTED AS NULL AND VOID BY THE STATE OF FLORIDA DBPR.
  
 2. MP1.1: UOTSIDE AIR CALCULATIONS REFERENCE THE 2003
 IMC. PLEASE CORRECTLY REFERENCE 2004 FBC,M IN
 ACCORDANCE WITH FS 553.73.
  
 3. MP1.1: OUTSIDE AIR CALCULATIONS REFERENCE AN EXHAUST
 SCHEDULE. NO SUCH SCHEDULE COULD BE FOUND ON PLANS.
 PROVIDE MISSING INFORMATION AS COMPLIANCE WITH FBC,M
 TABLE 403.3 IS REQUIRED BY FBC,EB 609.1.
  
 4. MP1.1: EXISTING HVAC EQUIPMENT SCHEDULE LISTS A
 "CHILLED WATER SPLIT SYSTEM." THE EQUIPMENT SHOWN ON
 PLANS IS EITHER A SPLIT SYSTEM OR PART OF A CHILLED
 WATER SYSTEM. IT IS NOT BOTH. THE MODEL NUMBER LISTED
 ON PLAN FOR AH-1 INDICATES THIS IS A CHILLED WATER
 SYSTEM. THAT WOULD MEAN THAT THERE IS NO EXISTING ROOF
 MOUNTED CONDENSING UNIT INVOLVED IN THE SCOPE OF THIS
 WORK. ALSO, THERE IS NO AH-2 SHOWN ON PLANS. IT SHOULD
 NOT BE ON THE EXISTING EQUIPMENT SCHEDULE. PLEASE MAKE
 CORRECTIONS AND CLARIFY AS NEEDED TO ACCURATELY REFLECT
 THE SCOPE OF WORK AND EXISTING CONDITIONS. FBC
 106.1.1.
 NOTE: EXISTING CU-1 IS ALSO SHOWN OP PG E1.1.
 COORDINATE ANY CORRECTIONS ON THIS PAGE WITH ELECTRICAL
 PLANS.
  
 5. MP1.1: PLAN SHOWS DUCT SMOKE DETECTOR IN RETURN DUCT
 FOR UNIT SHUT DOWN. DUCT SMOKE DETECTORS SHALL BE
 INSTALLED IN SUPPLY AIR SYSTEMS IN ACCORDANCE WITH
 FBC,M 606.2.1. ALSO, DUCT DETECTOR(S) SHALL BE
 CONNECTED TO THE BUILDING FIRE ALARM SYSTEM IN
 ACCORDANCE WITH FBC,M 606.4.1. CONSULT LANDLORD
 REGARDING CONNECTION TO EXISTING FIRE ALARM SYSTEM.
  
 6. MP1.1: TOILET ROOM EXHAUST FANS SHALL BE
 INTERCONNECTED WITH AH-1 TO ENSURE ALL AIR SUPPLIED TO
 THESE SPACES IS EXHAUSTED IN ACCORDANCE WITH FBC,M
 403.2.1(3). PROVISIONS SHALL ALSO BE MADE TO ENSURE
 THAT VENTILATION IS PROVIDED WHENEVER THESE SPACES ARE
 OCCUPIED IN ACCORDANCE WITH FBC,M 401.3.
  
 7. MP1.1: PROVIDE AIR BALANCE SCHEDULE SHOWING SUPPLY,
 RETURN AND EXHAUST TOTALS. THE SPACE SHALL BE
 PRESSURIZED WITH RESPECT TO THE OUTDOORS IN ACCORDANCE
 WITH FBC 13-409.1.ABC.2.
  
 8. MP1.1: PROVIDE SHUTOFF DAMPER CONTROLS FOR OUTSIDE
 AIR INTAKE DUCT IN ACCORDANCE WITH FBC
 13-409.1.ABC.3.3.
  
 9. MP1.1: CONDENSATE IS SHOWN DISCHARGING INTO A MOP
 SINK. CONDENSATE DRAINS SHALL DISCHARGE TO AN APPROVED
 PLACE OF DISPOSAL IN ACCORDANCE WITH FBC,M 307.2.1. A/C
 CONDENSATE SHALL NOT DISCHARGE INTO THE SANITARY SEWER
 SYSTEM IN ACCORDANCE WITH WPB MUNICIPAL CODE SECTION
 90-125(5).
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]