Plan Review Notes
Plan Review Notes For Permit 07100039
Permit Number 07100039
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-10-04 11:25:57***DENIED***
  
 1) MORE INFORMATION IS REQUIRED REGARDING THE REAR
 EXIT. MEANS OF EGRESS WOULD SUGGEST PERSONS PASSING
 THROUGH TWO (2) STORAGE ROOMS WITH THE POSSIBILITY OF
 BATHROOM DOORS CAUSING AN OBSTRUCTION. PLEASE SHOW
 COMPLIANCE WITH NFPA 101, SEC. 7.5.1.6.
  
 2) ILLUSTRATE AN ADDRESS ON THE BUILDING NEW OR
 EXISTING THAT COMPLIES WITH CITY OF WEST PALM BEACH
 REQUIREMENTS FOR COMMERCIAL BUILDINGS. CHARACTERS TO BE
 MINIMUM OF 6"IN HEIGHT AND CONTRASTING TO THE
 BACKGROUND. SUITE NUMBERS TO BE AT LEAST 3" IN HEIGHT.
 SHEET A3.1
  
 3) DUCT SMOKE DETECTORS TO BE LOCATED IN SUPPLY DUCT
 AND SHALL INITIATE A GENERAL FIRE ALARM IN ACCORDANCE
 WITH LOCAL REQUIREMENTS.
  
 4) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
 5) PLEASE INDICATE MINIMUM INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILING IN TERMS OF CLASS
 A,B OR C.
  
 6) BUILDING FIRE PROTECTION EQUIPMENT SHALL BE
 MAINTAINED DURING WORK.
  
 7) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR FIRE
 SPRINKLER AND FIRE ALARM REMODEL. PLANS MENTION FIRE
 ALARM EQUIPMENT BUT THIS IS NOT SHOWN ON DRAWINGS.
 SHEET E1.1
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756