Date |
Text |
2007-10-02 16:58:51 | ** DENIED *** |
| |
| FRESH PRODUCE CLOTHING STORE: |
| |
| 1) NOTE: PLEASE BE SURE TO COORDINATE ACTUAL SUITE |
| NUMBER ONTO TITLE BLOCKS OF PLANS INCLUDING TITLE COVER |
| SHEET. |
| SHOWS SUITE B-13, WHEN THE SUITE/UNIT # IS 132. PLEASE |
| ADJUST. |
| FAC 61G1-16.004, 61G15-23.002, FBC 110.1.2, 106.1.2 |
| |
| 2) NOTE: PLEASE SEE MISSING LICENSE INFORMATION FOR |
| ARCHITECTURAL FIRM AS REQUIRED UNDER FLORIDA |
| ADMINISTRATIVE CODE 61G1-16.004 AND AS REQUIRED PER |
| FLORIDA STATUTES 481.219. |
| THIS IS REQUIRED FOR ALL TRADES AND FOR ALL SHEETS |
| WHICH CONTAINS REFERENCE TO THIS FIRM. |
| THIS IS KNOWN AS THE CERTIFICATE OF AUTHORIZATION |
| NUMBER OBTAINED THROUGH THE DEPARTMENT OF BUSINESS AND |
| PROFESSIONAL REGULATION. |
| |
| 3) NOTE: PLEASE SEE THE ENGINEERING FIRM AS LISTED ON |
| THE TITLE SHEET (TS) IS NOT THAT OF THE SAME |
| ENGINEERING FIRM LISTED ON ELECTRICAL SHEETS. PLEASE |
| CLARIFY WHICH FIRM IS BEING THE RESPONSIBLE DESIGNER OF |
| RECORD. |
| PLEASE SEE THIS FIRM AS LISTED ON SHEET TS IS MISSING |
| RELEVANT LICENSE INFORMATION PER FAC 61G15-23.002 AND |
| FS 471.023. |
| THIS IS REQUIRED FOR ALL TRADES AND FOR ALL SHEETS |
| WHICH CONTAINS REFERENCE TO THIS FIRM. |
| THIS IS KNOWN AS THE CERTIFICATE OF AUTHORIZATION |
| NUMBER OBTAINED THROUGH THE DEPARTMENT OF BUSINESS AND |
| PROFESSIONAL REGULATION. |
| |
| 4) NOTE: PLEASE SEE BUILDING REVIEW NOTES FOR SHEET S-1 |
| AND MISSING CERTIFICATE OF AUTHORIZATION NUMBER PER FAC |
| 61G15-23.002, FS 471.023. |
| ** THIS IS BEING NOTED FOR INFORMATION ONLY AND TO SEE |
| BUILDING REVIEW NOTES* |
| |
| 5) NOTE: PLEASE SEE THE FIXTURE LEGEND AS SUBMITTED AND |
| SHOWN ON SHEET A1.2 AND E1.1 DO NOT CORRELATE. PLEASE |
| COORDINATE THE TWO AND ADJUST ANY LIGHTING PERFORMANCE |
| CALCULATIONS ETC WHICH MAY CHANGE BASED ON THE |
| FIXTURES. |
| FBC 13-415.2 |
| FBC 106.1.2 ADMIN SECTION FOR COORDINATION. |
| |
| 6) NOTE: PLEASE PROVIDE INFORMATION ON THE OVER RIDE |
| SWITCH DEVICES BEING NOTED FOR EACH CONTACTED AT THE |
| CASH-WRAP DESK LOCATIONS. PLEASE SEE FBC |
| 13-415.1.ABC.1.1, .1.2. |
| PLEASE KNOW ANY OVER RIDES DEPENDING ON TYPE OF DEVICE |
| ARE LIMITED TO THE TIMES OF OVER RIDES. |
| PLEASE KNOW AS THE LIGHTING IN THE REAR OF SPACE IS |
| SHOWN AS EXISTING,IF THE SWITCHES AS SHOWN ARE GOING |
| TO BE NEW, THESE WOULD ALSO NEED TO COMPLY TO THE |
| SECTIONS AS NOTED ABOVE PER CHAPTER 13 FOR LIGHTING |
| CONTROLS. (ONLY IF NEW) 13-101. THE EXISTING RESTROOMS |
| DO INDICATE *E* FOR THE EXISTING CONTROLS FOR LIGHTING. |
| PLEASE SEE REAR ENTRANCE INTO SPACE. |
| PLEASE CLARIFY AND STATE/ADJUST ACCORDINGLY. |
| |
| 7) NOTE: PLEASE SEE LIGHTING CONTACTOR CIRCUITS SHOWN |
| ON C-1 WHICH SEEMS TO LIST 2-2 TWICE. AS PER PLANS AND |
| THE LOCATION AND IDENTIFICATION OF CIRCUITS AT FRONT |
| DOOR LOCATION THIS SEEMS THIS SHOULD BE 2-2, 2-4 AND |
| 2-6? PLEASE CLARIFY AND CORRELATE. |
| |
| 8) NOTE: PLEASE SEE TRACK LIGHTING LOADS AS SHOWN ON |
| FIXTURE LEGEND AND PER 220.43B DO NOT SEEM TO MATCH THE |
| ACTUAL AMPERAGE LOAD FOR ALL CIRCUITS AS SHOWN ON PANEL |
| SCHEDULE 2. PLEASE SEE CIRCUIT 2-16 FOR EXAMPLE AS THIS |
| ONLY INDICATES 7.5AMPS FOR LOAD. |
| PLEASE SEE OTHER CIRCUITS WITH THE SAME LENGTH OF TRACK |
| AND FIXTURES INDICATE 12.5AMPS FOR THE SAME? PLEASE |
| CORRELATE AND ADJUST AS NEEDED. |
| FBC 106.1.2, 106.3.5.1.2 |
| NEC 408.4, 215.5, 220 ETC. |
| |
| 8) NOTE: PLEASE SEE E0.2 AS THE COLOR CODING IS NOTED |
| FOR 277/480V AS (A) YELLOW, (B) BROWN, (C) ORANGE. |
| PLEASE KNOW THE COLOR CODING FOR 277/480V SYSTEMS IN |
| THE CITY OF WEST PALM BEACH SHALL BE BROWN (A), PURPLE |
| (B) AND YELLOW (C). |
| PLEASE SEE THE NEC ONLY INDICATES COLOR CODING OF |
| ORANGE FOR A HIGH-LEG. |
| PLEASE KNOW AS THE EXISTING BUILDINGS LOCATED IN THE |
| CITY OF WEST PALM BEACH AND THIS LOCATION ALREADY |
| CONTAINS CONDUCTORS FOR FEEDERS AND SERVICE AS BROWN, |
| PURPLE, YELLOW, ANY NEW WOULD NEED TO MATCH. |
| THE PLANS MENTIONS ALL EXISTS FOR THESE CONDUCTORS AND |
| THIS NOTE ON E0.2 SHOULD NOT AFFECT THIS PROJECT. |
| PLEASE KNOW THAT ANY CHANGES WOULD REQUIRE THESE COLOR |
| CODING. |
| NEC 90.4. |
| |
| ** PLEASE BE SURE TO SEE ANY POSSIBLE COMMENTS FROM |
| OTHER TRADES WHICH MAY AFFECT ELECTRICAL PLANS. |
| IF THERE ARE ANY QUESTIONS, PLEASE CONTACT THIS |
| OFFICE/REVIEWER. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |