Plan Review Notes
Plan Review Notes For Permit 07100039
Permit Number 07100039
Review Stop E
Sequence Number 1
Notes
Date Text
2007-10-02 16:58:51** DENIED ***
  
 FRESH PRODUCE CLOTHING STORE:
  
 1) NOTE: PLEASE BE SURE TO COORDINATE ACTUAL SUITE
 NUMBER ONTO TITLE BLOCKS OF PLANS INCLUDING TITLE COVER
 SHEET.
 SHOWS SUITE B-13, WHEN THE SUITE/UNIT # IS 132. PLEASE
 ADJUST.
 FAC 61G1-16.004, 61G15-23.002, FBC 110.1.2, 106.1.2
  
 2) NOTE: PLEASE SEE MISSING LICENSE INFORMATION FOR
 ARCHITECTURAL FIRM AS REQUIRED UNDER FLORIDA
 ADMINISTRATIVE CODE 61G1-16.004 AND AS REQUIRED PER
 FLORIDA STATUTES 481.219.
 THIS IS REQUIRED FOR ALL TRADES AND FOR ALL SHEETS
 WHICH CONTAINS REFERENCE TO THIS FIRM.
 THIS IS KNOWN AS THE CERTIFICATE OF AUTHORIZATION
 NUMBER OBTAINED THROUGH THE DEPARTMENT OF BUSINESS AND
 PROFESSIONAL REGULATION.
  
 3) NOTE: PLEASE SEE THE ENGINEERING FIRM AS LISTED ON
 THE TITLE SHEET (TS) IS NOT THAT OF THE SAME
 ENGINEERING FIRM LISTED ON ELECTRICAL SHEETS. PLEASE
 CLARIFY WHICH FIRM IS BEING THE RESPONSIBLE DESIGNER OF
 RECORD.
 PLEASE SEE THIS FIRM AS LISTED ON SHEET TS IS MISSING
 RELEVANT LICENSE INFORMATION PER FAC 61G15-23.002 AND
 FS 471.023.
 THIS IS REQUIRED FOR ALL TRADES AND FOR ALL SHEETS
 WHICH CONTAINS REFERENCE TO THIS FIRM.
 THIS IS KNOWN AS THE CERTIFICATE OF AUTHORIZATION
 NUMBER OBTAINED THROUGH THE DEPARTMENT OF BUSINESS AND
 PROFESSIONAL REGULATION.
  
 4) NOTE: PLEASE SEE BUILDING REVIEW NOTES FOR SHEET S-1
 AND MISSING CERTIFICATE OF AUTHORIZATION NUMBER PER FAC
 61G15-23.002, FS 471.023.
 ** THIS IS BEING NOTED FOR INFORMATION ONLY AND TO SEE
 BUILDING REVIEW NOTES*
  
 5) NOTE: PLEASE SEE THE FIXTURE LEGEND AS SUBMITTED AND
 SHOWN ON SHEET A1.2 AND E1.1 DO NOT CORRELATE. PLEASE
 COORDINATE THE TWO AND ADJUST ANY LIGHTING PERFORMANCE
 CALCULATIONS ETC WHICH MAY CHANGE BASED ON THE
 FIXTURES.
 FBC 13-415.2
 FBC 106.1.2 ADMIN SECTION FOR COORDINATION.
  
 6) NOTE: PLEASE PROVIDE INFORMATION ON THE OVER RIDE
 SWITCH DEVICES BEING NOTED FOR EACH CONTACTED AT THE
 CASH-WRAP DESK LOCATIONS. PLEASE SEE FBC
 13-415.1.ABC.1.1, .1.2.
 PLEASE KNOW ANY OVER RIDES DEPENDING ON TYPE OF DEVICE
 ARE LIMITED TO THE TIMES OF OVER RIDES.
 PLEASE KNOW AS THE LIGHTING IN THE REAR OF SPACE IS
 SHOWN AS EXISTING,IF THE SWITCHES AS SHOWN ARE GOING
 TO BE NEW, THESE WOULD ALSO NEED TO COMPLY TO THE
 SECTIONS AS NOTED ABOVE PER CHAPTER 13 FOR LIGHTING
 CONTROLS. (ONLY IF NEW) 13-101. THE EXISTING RESTROOMS
 DO INDICATE *E* FOR THE EXISTING CONTROLS FOR LIGHTING.
 PLEASE SEE REAR ENTRANCE INTO SPACE.
 PLEASE CLARIFY AND STATE/ADJUST ACCORDINGLY.
  
 7) NOTE: PLEASE SEE LIGHTING CONTACTOR CIRCUITS SHOWN
 ON C-1 WHICH SEEMS TO LIST 2-2 TWICE. AS PER PLANS AND
 THE LOCATION AND IDENTIFICATION OF CIRCUITS AT FRONT
 DOOR LOCATION THIS SEEMS THIS SHOULD BE 2-2, 2-4 AND
 2-6? PLEASE CLARIFY AND CORRELATE.
  
 8) NOTE: PLEASE SEE TRACK LIGHTING LOADS AS SHOWN ON
 FIXTURE LEGEND AND PER 220.43B DO NOT SEEM TO MATCH THE
 ACTUAL AMPERAGE LOAD FOR ALL CIRCUITS AS SHOWN ON PANEL
 SCHEDULE 2. PLEASE SEE CIRCUIT 2-16 FOR EXAMPLE AS THIS
 ONLY INDICATES 7.5AMPS FOR LOAD.
 PLEASE SEE OTHER CIRCUITS WITH THE SAME LENGTH OF TRACK
 AND FIXTURES INDICATE 12.5AMPS FOR THE SAME? PLEASE
 CORRELATE AND ADJUST AS NEEDED.
 FBC 106.1.2, 106.3.5.1.2
 NEC 408.4, 215.5, 220 ETC.
  
 8) NOTE: PLEASE SEE E0.2 AS THE COLOR CODING IS NOTED
 FOR 277/480V AS (A) YELLOW, (B) BROWN, (C) ORANGE.
 PLEASE KNOW THE COLOR CODING FOR 277/480V SYSTEMS IN
 THE CITY OF WEST PALM BEACH SHALL BE BROWN (A), PURPLE
 (B) AND YELLOW (C).
 PLEASE SEE THE NEC ONLY INDICATES COLOR CODING OF
 ORANGE FOR A HIGH-LEG.
 PLEASE KNOW AS THE EXISTING BUILDINGS LOCATED IN THE
 CITY OF WEST PALM BEACH AND THIS LOCATION ALREADY
 CONTAINS CONDUCTORS FOR FEEDERS AND SERVICE AS BROWN,
 PURPLE, YELLOW, ANY NEW WOULD NEED TO MATCH.
 THE PLANS MENTIONS ALL EXISTS FOR THESE CONDUCTORS AND
 THIS NOTE ON E0.2 SHOULD NOT AFFECT THIS PROJECT.
 PLEASE KNOW THAT ANY CHANGES WOULD REQUIRE THESE COLOR
 CODING.
 NEC 90.4.
  
 ** PLEASE BE SURE TO SEE ANY POSSIBLE COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL PLANS.
 IF THERE ARE ANY QUESTIONS, PLEASE CONTACT THIS
 OFFICE/REVIEWER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]