Plan Review Notes For Permit 07100028 |
Permit Number |
07100028 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-10-09 16:00:17 | | | | | APPLICATION #07100028 | | ELECTRICAL PLAN REVIEW | | 3900 GEORGIA AVENUE | | 10/9/07 | | WEST PALM BEACH, FL. | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND | | FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | 1} THE PROPERTY FOR WHICH THIS APPLICATION WAS | | SUBMITTED HAS MORE THAN ONE BUILDING. PROVIDE A SITE | | PLAN INDICATING WHICH BUILDING AND THE LOCATION THE | | PROPOSED SERVICE IS TO BE INSTALLED. ALSO NOTE 230.2 | | AND INDICATE COMPLIANCE WITH SAME. | | | | 2} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT | | CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE | | EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS | | EQUAL TO OR GREATER THAN THE AVAILABLE FAULT. | | | | 3} INDICATE COMPLIANCE WITH ARTICLE 230.70(A)(1), THE | | AHJ HAS DETERMINED THAT ?NEAREST POINT OF ENTRANCE? | | SHALL BE NO FARTHER THAN 8? OF UNPROTECTED CONDUCTORS. | | INDICATE COMPLIANCE WITH THIS ARTICLE ON THE PLAN. | | | | 4} THE GROUNDING ELECTRODE CONDUCTOR MUST COMPLY WITH | | 250.66 AND 250.50. INDICATE COMPLIANCE ON THE RISER | | DIAGRAM. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | | [email protected] |
|