Plan Review Notes
Plan Review Notes For Permit 07100021
Permit Number 07100021
Review Stop B
Sequence Number 3
Notes
Date Text
2007-11-27 19:04:35PROJECT: 2210 NORTH AUSTRALIAN AVENUE/#07100021
  
 PROJECT SCOPE: REMOVE/REPLACE DRYWALL INSULATION
 CABINETS & FLOORING DAMAGED BY WATER (22 APTS)
  
 CODE REVIEW:2004 FLORIDA EXISTING BUILDING CODE
 W/2006 REVISIONS
 2004 FLORIDA BUILDING CODE W/ 2006 REVISIONS
 CITY OF WEST PALM BEACH ADMINISTRATION AMENDMENTS,
 CHAPTER 1, 2004 EDITION
  
 STATUS: FAILED
  
 COMMENTS:
  
 1) A DESIGN PROFESSIONAL OR OWNER MUST ELECT A LEVEL OR
 LEVELS OF ALTERATION PURSUANT TO
 THE FOLLOWING CODE SECTION:
  
 FLORIDA EXISTING BUILDING CODE
  
 301.5 . A DESIGN PROFESSIONAL OR AN
 OWNER MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO SECTION
 303,304 & 305 OF THIS CODE.
  
  
 2) REQUIRE A NOTICE OF COMMENCEMENT AS PER THE
 FOLLOWING:
  
 FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) AS PER THE FBC 106.3.5, PLEASE PROVIDE THE FOLLOWING
 DATA:
  
 A) BUILDING CONSTRUCTION TYPE
 B) OCCUPANCY LOAD
 C) OCCUPANCY GROUP
 D) SPRINKLERED OR NON-SPRINKLERED
  
  
 4) THE SUBMITTED PLANS SHALL MEET THE MINIMUM
 REQUIREMENTS OF THE FOLLOWING:
  
 61G1-16.004 TITLE BLOCK.
 A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR
 INTERIOR DESIGN DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK
 MUST, AT A MINIMUM, CONTAIN THE FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT.
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING
 THE DOCUMENT.
  
  
 5) REQUIRE SPECIFICATIONS FOR THE INTERIOR FINISHES AND
 CARPETING AS PER THE FOLLOWING:
  
  
 FLORIDA EXISTINGBUILDING CODE
  
 503.1INTERIOR FINISHES.
 ALL NEWLY INSTALLED INTERIOR FINISHES SHALL COMPLY WITH
 THE FLAME SPREAD REQUIREMENTS OF THE FLORIDA BUILDING
 CODE, BUILDING.
  
 503.2CARPETING.
 NEW CARPETING USED AS AN INTERIOR FLOOR FINISH MATERIAL
 SHALL COMPLY WITH THE RADIANT FLUX REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 503.3MATERIALS AND METHODS.
 ALL NEW WORK SHALL COMPLY WITH MATERIALS AND METHODS
 REQUIREMENTS IN THE FLORIDA BUILDING CODE AND THE
 FLORIDA FIRE PREVENTION CODE AS APPLICABLE, THAT
 SPECIFY MATERIAL STANDARDS, DETAIL OF INSTALLATION AND
 CONNECTION, JOINTS, PENETRATIONS, AND CONTINUITY OF ANY
 ELEMENT, COMPONENT, OR SYSTEM IN THE BUILDING.
  
 6) PLEASE PROVIDE ENERGY CALCULATIONS AS PER CHAPTER 13
 OF THE FLORIDA BUILDING CODE:
  
 512.1MINIMUM REQUIREMENTS.
 ALTERATIONS SUBJECT TO THIS CHAPTER SHALL COMPLY
 WITH THE REQUIREMENTS OF CHAPTER 13 OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 7) PLEASE INDICATE SPECIFIC UNIT NUMBERS APPLICABLE TO
 THE SCOPE OF PROPOSED WORK.
  
 8) THE PROJECT VALUATION APPEARS TO BE LOW BASED ON THE
 MARSHALL AND SWIFT ESTIMATION GUIDE. PLEASE INCREASE
 NOTED VALUATION TO REFLECT THE SAME.
  
  
 PLAN REVIEW: KEN CONRAD
 PHONE: 561.805.6666
 E-MAIL: KCONRAD @WPB.ORG
  
  
  
  
  
  
  
  
  
  
  
  
  