Plan Review Notes
Plan Review Notes For Permit 07090849
Permit Number 07090849
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-10-11 10:25:21***DENIED***
  
 1) IF THE CONTRACT IS GREATER THAN $2,500.00, THE
 APPLICANT SHALL FILE WITH THE AHJ EITHER A RECORDED
 NOTICE OF COMMENCEMENT OR A NOTORIZED STATEMENT THAT
 THE NOTICE HAS BEEN FILED FOR RECORDING ALONG WITH A
 COPY THEREOF.
  
 2) FIRE DETECTION AND ALARM SYSTEMS WHICH COST MORE
 THAN $5.000.00 REQUIRE A PROFESSIONAL ENGINEER TO SIGN
 HIS OR HER SEAL TO ALL PLANS, SPECIFICATIONS ETC. TO BE
 FILED FOR PUBLIC RECORD.
  
 3) DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE
 ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS.
  
 4) MORE INFORMATION IS REQUIRED. PLANS MENTION FLOWS
 AND TAMPERS HOWEVER THIS IS NOT SHOWN ON LEGEND. IF
 EQUIPMENT IS EXISTING WITH NO CHANGE, PLEASE PROVIDE
 THAT INFORMATION ON PLANS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756