2007-10-10 14:37:00 | DENIED |
| REFERENCE: |
| ** FBC-2004 WITH 05 & 06 REVISIONS, PLUMBING. |
| ** FBC-2004 CHAPTER 1, THE CITY OF |
| WEST PALM BEACH AMENDMENTS. |
| ** FBC-2004 WITH 06 REVISIONS CHAPTER 11, FLORIDA |
| ACCESSIBILITY CODE. |
| ** FLORIDA ADMINISTRATIVE CODE (FAC). |
| ** FLORIDA STATUTES (FS). |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| GAS/PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE: |
| |
| 1. 1. MORE INFORMATION IS REQUIRED DUE TO THE FACT |
| THAT A PLUMBING PERMIT IS BEING APPLIED FOR. PLEASE |
| PROVIDE THE FOLLOWING INFORMATION IF IT PERTAINS TO |
| YOUR JOB. |
| |
| A} IF PLUMBING LAYOUT IS THE SAME WITH NO CHANGES, |
| PLEASE INDICATE THIS ON THE RESUBMITTED DRAWINGS. |
| |
| B} IF PLUMBING LAYOUT IS THE SAME AND THE PLUMBING |
| FIXTURES ARE TO BE CHANGED, PLEASE INDICATE ON THE |
| RESUBMITTED DRAWINGS. "EXACT FIXTURE CHANGEOUT ONLY" |
| AND CLEARLY INDICATE WHAT FIXTURES ARE GOING TO BE |
| CHANGED. |
| |
| C} IF THE NEW PROPOSED PLUMBING LAYOUT IS DIFFERENT |
| FROM THE EXISTING PLEASE SUBMIT THE FOLLOWING ON |
| SEPERATE DRAWINGS. |
| A) EXISTING FLOOR PLAN LAYOUT. |
| B) NEW PROPOSED FLOOR PLAN LAYOUT AND PLEASE FOLLOW |
| WHAT IS REQUIRED IN COMMENT #2. |
| |
| 2. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.4 |
| RESIDENTIAL (ONE AND TWO-FAMILY) PLEASE SUBMIT A |
| PLUMBING SANITARY ISOMETRIC RISER DIAGRAM INDICATING |
| ALL WASTE, VENTS, TRAPS AND SIZES WITH CLEANOUT |
| LOCATIONS. |
| |
| 3. PER FBC-2004 CHAPTER 1, SECTION |
| 106.1 SUBMITTAL DOCUMENTS. CONSTRUCTION |
| DOCUMENTS, SPECIAL INSPECTION AND |
| STRUCTURAL OBSERVATION PROGRAMS, AND |
| OTHER DATA SHALL BE SUBMITTED IN TWO OR |
| MORE SETS WITH EACH APPLICATION FOR A |
| PERMIT. |
| NOTE: ONLY ONE SET OF DRAWING WAS SUBMITTED. |
| |
| 4. AT A MINIMUM THE PLANS MUST CLEARLY REFLECT WHAT IS |
| ON THE PERMIT APPLICATION. THE SUBMITTED PLANS DO NOT |
| DO THIS. PER FBC-2004 CHAPTER 1, SECTION 106.1.1 |
| INFORMATION ON CONSTRUCTION |
| DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL |
| BE OF SUFFICIENT CLARITY TO INDICATE THE |
| LOCATION, NATURE AND EXTENT OF THE WORK |
| PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| CONFORM TO THE PROVISIONS OF THIS CODE |
| AND RELAVENT LAWS, ORDINANCES, RULES AND REGULATIONS, |
| AS DETERMINED BY THE |
| BUILDING OFFICIAL. |
| |
| 5. FBC-2004 CHAPTER 1,SECTION 106.3.4.3: |
| THE PERSON RESPONSIBLE FOR THE DESIGN OF |
| THE DRAWING SHALL CLEARLY PRINT AND SIGN |
| NAME, AND ALSO DATE DRAWING. PLEASE DO |
| THIS PRIOR TO RESUBMITTING. |
| |
| 6. PER FC 713.13 (1) THRU (6): A NOTICE OF |
| COMMENCEMENT IS REQUIRED FROM THE - PALM BEACH COUNTY |
| COURTHOUSE - 4TH FLOOR RECORDING DEPT. 205 N. DIXIE |
| HWY., BEFORE A PERMIT CAN BE ISSUED. |
| |
| END OF COMMENTS: |
| |