2007-10-23 14:02:55****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.CHANGES TO THE PLAN ARE TO BE DONE BY THE ARCHITECT
 OR ENGINEER SEALING THE PLAN.IT APPEARS THAT THE
 ARCHITECT HAS REVISED THE ENGINEER'S PLAN.AS ONE
 CHANGE MAKES THE REVISED PLAN LESS CONSERVATIVE (OTHER
 CHANGES TO THE SIZE MADE THE AWNINGS SMALLER WITH ONE
 EXCEPTION, WHICH INCREASED THE SIZE OF THE AWNING),
 THIS MUST BE APPROVED BY THE AWNING ENGINEER.
  
 2.SHEET 1, ENGINEERING EXPRESS NOTE 8 STATES DESIGN
 CRITERIA AS ASCE7-98; THIS SHOULD BE ASCE7-02 FBC
 CHAPTER 35.
  
 3.IT IS NOT CLEAR IF ADDING A SIDE VALANCE AFFECTS
 THE ENGINEERING.HAVE THE ENGINEER REVISE THE PLAN TO
 INCLUDE THE CHANGES REQUESTED BY THE ARCHITECT.
  
 4.THE ENGINEER SPECIFIES 48" MINIMUM HEIGHT; DOES HE
 MEAN MAXIMUM?PLEASE ADDRESS BY REVISING THE NOTE OR,
 IF IT IS INDEED A MINIMUM SIZE, REVISE THE ENGINEERING
 AS THE ARCHITECT IS SPECIFYING AWNINGS WHICH ARE LESS
 THAN 48" IN HEIGHT.
  