Plan Review Notes For Permit 07090780
Permit Number 07090780
Review Stop E
Sequence Number 2
Notes
Date Text
2008-03-10 08:50:06** DENIED REVIEW **
  
  
 1) NOTE: PLEASE SEE 210.52D, 210.11C3 FOR MISSING
 DEDICATE BATH CIRCUIT.
  
 2) NOTE: PLEASE SEE EXISTING HOUSE PANEL IS NOT SHOWING
 ANY BREAKERS FOR THE NEW SUB PANELS.
 408.4, ETC
 FBC 106.3.5.4
  
 3) NOTE: THE FOOTER STEEL AT THE DETACHED BUILDINGS ARE
 REQUIRED TO BE PART OF THE GROUNDING ELECTRODE
 SYSTEMS.
 250.50, 250.32
  
 4) NOTE: PLANS DO NOT SHOW THE LOCATIONS OF THE PANELS
 DISCONNECTS AT THE DETACHED BUILDING. 225.31-225.39,
 110.26, 240.24
  
  
  
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]