2008-03-10 08:50:06 | ** DENIED REVIEW ** |
| |
| |
| 1) NOTE: PLEASE SEE 210.52D, 210.11C3 FOR MISSING |
| DEDICATE BATH CIRCUIT. |
| |
| 2) NOTE: PLEASE SEE EXISTING HOUSE PANEL IS NOT SHOWING |
| ANY BREAKERS FOR THE NEW SUB PANELS. |
| 408.4, ETC |
| FBC 106.3.5.4 |
| |
| 3) NOTE: THE FOOTER STEEL AT THE DETACHED BUILDINGS ARE |
| REQUIRED TO BE PART OF THE GROUNDING ELECTRODE |
| SYSTEMS. |
| 250.50, 250.32 |
| |
| 4) NOTE: PLANS DO NOT SHOW THE LOCATIONS OF THE PANELS |
| DISCONNECTS AT THE DETACHED BUILDING. 225.31-225.39, |
| 110.26, 240.24 |
| |
| |
| |
| |
| |