Plan Review Notes
Plan Review Notes For Permit 07090780
Permit Number 07090780
Review Stop E
Sequence Number 1
Notes
Date Text
2007-10-20 10:28:48 
 PLANS WERE NOT SENT TO ELECTRICAL SFR UNTIL 10/19
2007-10-20 10:24:102007-10-20 10:24:10
  
 ** DENIED **
  
  
 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
  
 2) NOTE: PLEASE SEE EACH BLDG IS SHOWING AN ELECTRICAL
 RISER OF A SEPARATE ELECTRICAL SERVICE WHICH IS NOT
 PERMITTED. 230.2.
 PLEASE SEE THAT THE PANEL SCHEDULES AS SUBMITTED ON
 EACH DO NOT ACCURATELY REFLECT ANY OF THE ELECTRICAL ON
 PLANS.
  
 3) NOTE: PLEASE SEE 225.31-225.39 AS SEPARATE
 SUB-PANELS AT EACH BUILD FED FROM THE MAIN HOUSE WOULD
 BE REQUIRED. THIS IS ONLY BASED ON USE AND PERMITTED
 USE FROM ZONING AND OTHER TRADES.
 AS NONE IS SHOWN, REVIEW CAN NOT BE DONE. (LOCATION,
 SIZE, OVER CURRENT PROTECTION, ETC)
 PLEASE SEE 240.4, 310.16 AND 408.4 FOR REQUIRED PANEL
 SCHEDULE(S) ETC
 FBC 106.3.5.4, 106.1.2
  
 4) NOTE: PLEASE SEE 250.32 AND 250.50 FOR GROUNDING
 ELECTRODE SYSTEM REQUIRED AT EACH STRUCTURE.
 THIS WILL INCLUDE GROUNDING FROM THE PANELS/DISCONNECTS
 FROM NOTE #3 ABOVE TO FOOTER STEEL, AND ANY METAL COLD
 WATER PIPE.
 THESE ARE THE *MINIMUM* THAT ARE REQUIRED.
  
 5) NOTE: PLEASE SEE MISSING BATH ROOM REQUIRED
 DEDICATED CIRCUIT(S) PER 210.52D, 210.8A2, 210.11C3.
 MUST BE 20AMP AND #12.
 THEREARE NONE SHOWN ON PLANS, AND AS NEW PANELS FOR
 EACH BUILDING WILL BE REQUIRED, NO REVIEW CAN BE DONE
 OF THESE.
  
 6) NOTE: PLEASE SEE MISSING SMOKE ALARMS PER NFPA-72
 11.5.1.1.1, 11.8.3
 MUST BE INSTALLED AS THESE ARE CLEARLY ADAPTABLE
 SLEEPING ROOMS/APARTMENTS.
 PLEASE SEE THE NEXT COMMENT ALSO FOR 210.12.
  
 7) NOTE: PLEASE SEE AS THE PLANS APPEAR TO SHOW AND
 LEND TO APARTMENT USE AND THE FACT THAT THESE ROOMS ARE
 ADAPTABLE SLEEPING ROOMS, ARC FAULT PROTECTION WILL BE
 REQUIRED PER 210.12
  
 8) NOTE: PLEASE SEE THAT NO WHITE-OUT OF ANY KIND MAY
 BE PLACED ON PLANS.
 FS 481, FBC 106.1
  
 9) NOTE: PLEASE SEE PLUMB PLANS INDICATE TWO SINKS,
 HOWEVER ONLY ONE IS SHOWN ON PLANS. THIS WILL DIRECTLY
 AFFECT THE ELECTRICAL REQUIREMENTS IF A KITCHEN IS
 BEING INSTALLED OR WIRED ON-SITE. A FIELD INSPECTION OF
 ELECTRICAL SYSTEMS OF WHICH MAY ALREADY BE WIRED ETC
 MAY BE DONE TO ACCURATELY COME UP WITH WHAT WORK IS
 DONE, TO BE DONE, USE ETC.
 PLANS DO NOT CORRELATE FOR USE.
 ARCHITECT TO SEE FS 481 FOR DESIGN RESPONSIBILITY.
 PLANS MAY BE RETAINED BY THIS OFFICE AND PLACED WITH
 OTHER PLANS RETAINED IN FILE FOR THIS DESIGNER. PLANS
 ARE REQUIRED TO BE DESIGNED FOR ACCURATE USE, AND THE
 MINIMUM CODE(S).
  
 10) NOTE: PLEASE SEE AS PLANS INDICATE A WATER HEATER
 WITH WHITE OUT OVER IT, PLEASE INCLUDE ON PLANS IF SO
 INSTALLED OR PROPOSED.
 PLEASE SEE 422.17 AS THE WATER HEATER MAY NOT BE IN A
 CLOSET.
  
 11) NOTE: PLEASE SEE DEPENDING ON USE; PLEASE SEE ALL
 OF 210.52 WHICH SEVERAL ITEMS MAY BE REQUIRED.
  
 ** PLEASE KNOW PLANS ARE REQUIRED TO BE DESIGNED TO
 *MINIMUM* STANDARDS FOR CODE COMPLIANCE FOR USE AND IT
 IS THE RESPONSIBILITY OF ALL PERSONS INVOLVED.
  
 ** PLEASE KNOW AS THERE ARE NUMEROUS ITEMS NOT YET
 SHOWN OR SUBMITTED UNDER THE DESIGN, THERE MAY BE NEW
 COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT BE MADE
 AT THIS TIME.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]