2007-10-20 10:28:48 | |
| PLANS WERE NOT SENT TO ELECTRICAL SFR UNTIL 10/19 |
2007-10-20 10:24:10 | 2007-10-20 10:24:10 |
| |
| ** DENIED ** |
| |
| |
| 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH |
| ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS |
| UNDER THE NEW CODES ADOPTED BY THE STATE. |
| PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| AFFECT DESIGNS FOR ALL TRADES. |
| PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| REVIEWER AT A MINIMUM. |
| 2004 FBC W/ 2006 REVISIONS |
| 2005 NFPA-70 |
| 2002 NFPA-72 |
| |
| 2) NOTE: PLEASE SEE EACH BLDG IS SHOWING AN ELECTRICAL |
| RISER OF A SEPARATE ELECTRICAL SERVICE WHICH IS NOT |
| PERMITTED. 230.2. |
| PLEASE SEE THAT THE PANEL SCHEDULES AS SUBMITTED ON |
| EACH DO NOT ACCURATELY REFLECT ANY OF THE ELECTRICAL ON |
| PLANS. |
| |
| 3) NOTE: PLEASE SEE 225.31-225.39 AS SEPARATE |
| SUB-PANELS AT EACH BUILD FED FROM THE MAIN HOUSE WOULD |
| BE REQUIRED. THIS IS ONLY BASED ON USE AND PERMITTED |
| USE FROM ZONING AND OTHER TRADES. |
| AS NONE IS SHOWN, REVIEW CAN NOT BE DONE. (LOCATION, |
| SIZE, OVER CURRENT PROTECTION, ETC) |
| PLEASE SEE 240.4, 310.16 AND 408.4 FOR REQUIRED PANEL |
| SCHEDULE(S) ETC |
| FBC 106.3.5.4, 106.1.2 |
| |
| 4) NOTE: PLEASE SEE 250.32 AND 250.50 FOR GROUNDING |
| ELECTRODE SYSTEM REQUIRED AT EACH STRUCTURE. |
| THIS WILL INCLUDE GROUNDING FROM THE PANELS/DISCONNECTS |
| FROM NOTE #3 ABOVE TO FOOTER STEEL, AND ANY METAL COLD |
| WATER PIPE. |
| THESE ARE THE *MINIMUM* THAT ARE REQUIRED. |
| |
| 5) NOTE: PLEASE SEE MISSING BATH ROOM REQUIRED |
| DEDICATED CIRCUIT(S) PER 210.52D, 210.8A2, 210.11C3. |
| MUST BE 20AMP AND #12. |
| THEREARE NONE SHOWN ON PLANS, AND AS NEW PANELS FOR |
| EACH BUILDING WILL BE REQUIRED, NO REVIEW CAN BE DONE |
| OF THESE. |
| |
| 6) NOTE: PLEASE SEE MISSING SMOKE ALARMS PER NFPA-72 |
| 11.5.1.1.1, 11.8.3 |
| MUST BE INSTALLED AS THESE ARE CLEARLY ADAPTABLE |
| SLEEPING ROOMS/APARTMENTS. |
| PLEASE SEE THE NEXT COMMENT ALSO FOR 210.12. |
| |
| 7) NOTE: PLEASE SEE AS THE PLANS APPEAR TO SHOW AND |
| LEND TO APARTMENT USE AND THE FACT THAT THESE ROOMS ARE |
| ADAPTABLE SLEEPING ROOMS, ARC FAULT PROTECTION WILL BE |
| REQUIRED PER 210.12 |
| |
| 8) NOTE: PLEASE SEE THAT NO WHITE-OUT OF ANY KIND MAY |
| BE PLACED ON PLANS. |
| FS 481, FBC 106.1 |
| |
| 9) NOTE: PLEASE SEE PLUMB PLANS INDICATE TWO SINKS, |
| HOWEVER ONLY ONE IS SHOWN ON PLANS. THIS WILL DIRECTLY |
| AFFECT THE ELECTRICAL REQUIREMENTS IF A KITCHEN IS |
| BEING INSTALLED OR WIRED ON-SITE. A FIELD INSPECTION OF |
| ELECTRICAL SYSTEMS OF WHICH MAY ALREADY BE WIRED ETC |
| MAY BE DONE TO ACCURATELY COME UP WITH WHAT WORK IS |
| DONE, TO BE DONE, USE ETC. |
| PLANS DO NOT CORRELATE FOR USE. |
| ARCHITECT TO SEE FS 481 FOR DESIGN RESPONSIBILITY. |
| PLANS MAY BE RETAINED BY THIS OFFICE AND PLACED WITH |
| OTHER PLANS RETAINED IN FILE FOR THIS DESIGNER. PLANS |
| ARE REQUIRED TO BE DESIGNED FOR ACCURATE USE, AND THE |
| MINIMUM CODE(S). |
| |
| 10) NOTE: PLEASE SEE AS PLANS INDICATE A WATER HEATER |
| WITH WHITE OUT OVER IT, PLEASE INCLUDE ON PLANS IF SO |
| INSTALLED OR PROPOSED. |
| PLEASE SEE 422.17 AS THE WATER HEATER MAY NOT BE IN A |
| CLOSET. |
| |
| 11) NOTE: PLEASE SEE DEPENDING ON USE; PLEASE SEE ALL |
| OF 210.52 WHICH SEVERAL ITEMS MAY BE REQUIRED. |
| |
| ** PLEASE KNOW PLANS ARE REQUIRED TO BE DESIGNED TO |
| *MINIMUM* STANDARDS FOR CODE COMPLIANCE FOR USE AND IT |
| IS THE RESPONSIBILITY OF ALL PERSONS INVOLVED. |
| |
| ** PLEASE KNOW AS THERE ARE NUMEROUS ITEMS NOT YET |
| SHOWN OR SUBMITTED UNDER THE DESIGN, THERE MAY BE NEW |
| COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT BE MADE |
| AT THIS TIME. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |