Plan Review Notes
Plan Review Notes For Permit 07090780
Permit Number 07090780
Review Stop B
Sequence Number 1
Notes
Date Text
2007-11-03 13:01:55 
  
 DENIED
  
 1)PLANS AND SPECIFICATIONS DESIGN PARAMETERS SHALL
 COMPLY WITH THE 2004 FLORIDA BLDG CODE WITH 2006
 AMENDMENTS PER 106.1.1 FBC*
  
 2)PROVIDE THE WIND DESIGN DATA THAT APPLIES TO
 BUILDING PER 1603.1.4 FBC
  
 3)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*
  
 4)IF THE ACCESSORY BUILDINGS ARE DEEMED TO BE LIVING
 SPACES THE STATE OF FLORIDA REQUIRES COLLECTION OF A
 RADON SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON
 UNDER ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL
 BE ADDED TO THE PERMIT APPLICATION FEES.
  
 NOTE: FEES ARE DUE IN THE AMOUNT OF $785.96FOR
 INCREASED VALUE THIS AMOUNT IS REQUIRED TO BE PAID
 PRIOR TO FURTHER PLAN REVIEW. THESE FEES ARE FOR
 UTILITY BUILDINGS AND AS ABOVE IF DEEMED RESIDENCE
 USAGE THE FEES WILL BE INCREASED.
  
 5)PROVIDE DRAWINGS AND SPECIFICATIONS THAT ARE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION,NATURE, AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE PER 106.1.1
 FBC* PLEASE NOTE THAT PERMIT APPLICATION STOP WORK
 ORDER AND NOTICE OF VIOLATION ALL INDICATE THAT
 BUILDINGS ARE OF CBS CONSTRUCTION.
  
 6)IF BUILDINGS ARE RESIDENCESTWO COPIES OF ENERGY
 CALC'S PER 13-101.2.2 FBC. BE SURE THAT THEY ARE SIGNED
 AND DATED BY PREPARER AND OWNER/AGENT PRIOR TO
 SUBMITTAL
  
 7)PROVIDE SCHEDULE FOR PRECAST LINTEL THAT WILL BE
 USED AND OPENING SIZES TO COMPLY WITH 2104.1.5 FBC FOR
 MIN BEARING
  
 8)DRAWINGS SHALL SHOW THE MINIMUM DEPTH OF FOUNDATION
 ON THE WALL SECTIONS PER R403.1.4 FBC RES.
  
 9)THE PERMIT APPLICATION SHALL INCLUDE TWO COPIES OF
 EACH PRODUCT APPROVAL THAT IS RELEVANT PER 9B-72. THESE
 SHOULD INCLUDE THE FLORIDA STATE APPROVAL COVER PAGES.
 ALL CAN BE FOUND ON WWW.FLORIDABUILDING.ORG
  
 10)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE
 9B-72 (PRODUCT APPROVALS) SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
 11)THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA
 STATE PRODUCT APPROVAL COVER
 SHEETS WHEN AVAILABLE. THEY CAN BE SEARCHED FOR ON
 WWW.FLORIDABUILDING.ORG.WHEN AVAILABLE AND NOT
 SUBMITTED APPLICATIONS WILL BE DENIED
  
 12) NO PRODUCT APPROVALS WERE SUBMITTED FOR LINTELS,
 CONNECTORS AND STRAPS, WINDOWS, DOORS AND ROOFING
 MATERIAL, IN LUE OF PRODUCT APPROVALS STRAPS/CONNECTORS
 MAY BE LISTED IN A SCHEDULE ON THE DRAWINGS COMPLETE
 WITH THE STATEWIDE PRODUCT APPROVAL NUMBERS OR SUBMIT
 SIMPSON TIE?S COMPLETE FLORIDA INDEX WITH CONNECTORS TO
 BE USED HIGHLIGHTED
  
 13)PROVIDE 2 COMPLETE SETS OF ALL DRAWINGS AND
 SUBMITTALS
  
 14)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 15)ADDITIONAL PERMITS WILL BE REQUIRED FOR PLUMBING,
 ELECTRICAL AND MECHANICAL AND ROOFING
  
 16)REMOVE ALL OLD PAGES AND RESUBMIT 2 COMPLETE SETS
 OF NEW DRAWINGS AND INCLUDE 1 COPY OF THE OLD PAGES
 ONLY FOR REFERENCE
  
 17)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED,
 IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE
 ACTUAL PERMIT SETS OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561) 233-5025 FOR MORE
 INFORMATION.
  
 18)UNTIL INSPECTION OF THE INTERIOR OF THESE
 BUILDINGS IS UNDERTAKEN AND PLANS CAN BE VERIFIED TO BE
 TRUE, A COMPLETE PLAN REVIEW CANNOT BE MADE AND MORE
 COMMENTS MAY BE FORTHCOMING. FOR ANINSPECTION OF
 PREMISES PLEASE CALL CHIEF BUILDING INSPECTOR KEN
 CONRAD AT (561) 805-6666
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716