Plan Review Notes
Plan Review Notes For Permit 07090774
Permit Number 07090774
Review Stop E
Sequence Number 2
Notes
Date Text
2007-10-26 07:50:38 
  
  
 DENIED/INCOMPLETE INFORMATION
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 SAME COMMENT AS THE PREVIOUS REVIEW:
  
 1} PER 106.1 FBC AS AMMENDED, PLANS ARE REQUIRED FOR
 THE SCOPE OF WORK APPLIED FOR. THE SERVICE RELOCATION
 AND A/C CIRCUIT INDICATED ON SHEET D3 OF 3 REQUIRE AN
 ELECTRICAL PERMIT AND PLANS. SUBMIT SAME.* THE
 RELOCATED SERVICE REQUIRES A RISER DIAGRAM AND AN
 ELECTRICAL PERMIT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]