2008-08-12 10:22:41 | |
| **DENIEDREVISION** |
| |
| ** PLEASE SEE SOME ITEMS FROM REVIEW DATED 6/25 ARE |
| STILL IN NEED OF ADDRESSING. |
| |
| 1) NOTE:PLEASE SEE PREVIOUS REVIEW WHICH STATED THE |
| REVISED ENERGY CALCULATIONS WERE NEEDED DUE TO LIGHTING |
| ETC BEING REVISED ON PLANS. THE RESPONSE LETTER |
| MENTIONS TO SEE REVISED CALCULATIONS. HOWEVER PLEASE |
| SEE THE PACKAGE AS ONLY THE CERTIFICATION SHEETS ALONG |
| WITH SUMMARY SHEETS WERE SUBMITTED. PLEASE SEE SHEET |
| TWO WHICH STATES THE INPUT DATA REPORT MUST BE |
| SUBMITTED ALONG WITH COMPLIANCE REPORT. AS NO INPUT |
| DATA REPORT WAS SUBMITTED A REVIEW OF THE SPECIFIC |
| ITEMS ON PLANS CAN NOT BE REVISED AT THIS TIME. |
| PLEASE BE SURE ALL REVISED LIGHTING ON PLANS ALONG WITH |
| ALL OTHER COMPONENTS OF BUILDING REFLECTS THE INPUT |
| DATA REPORT. |
| 13-400.3B, 13-415.2, 13-415.2.ABC.1.1, .1.2, AND .1.3. |
| |
| ** PLEASE SEE THE *CERTIFICATION SHEET* WHICH REQUIRES |
| THE SIGNING, SEALING DATING AND OTHER INFORMATION TO BE |
| COMPLETED. AS THESE DOCUMENTS ARE ALSO PART OF |
| INFORMATION SENT TO THE STATE, THE CERTIFICATION SHEET |
| NEEDS TO BE COMPLETED. SIGNING AND SEALING THE COVER |
| SHEET DOES NOT PROVIDE THE INFORMATION ON THE |
| CERTIFICATION SHEETS. |
| 13-103.1, FS 471.025 |
| |
| 2) NOTE: AS NOTED ON PREVIOUS REVIEW WHY WAS THE |
| PHOTO-METRICS BEING SUBMITTED IF LIGHTING WAS NOT BEING |
| REVISED? THE RESPONSE MENTIONS *INDUCTION LIGHTING * |
| ETC. |
| PLEASE BE SURE THERE IS COORDINATION BETWEEN ALL |
| REVISED LIGHTING PLANS, PHOTO-METRICS AND CALCULATIONS |
| AS NOTED ABOVE. |
| FOR EXAMPLE: |
| PLEASE SEE THE QUARTZ LIGHT FIXTURES AS NOTED ON |
| PHOTO-METRICS ARE NOT THE SAME AS THE FIXTURES LISTED |
| ON FIXTURE LEGEND FOR MANUFACTURE, WATTAGE ETC |
| |
| FOR EXAMPLE: |
| PLEASE TAKE A LOOK AT THE FIXTURE DESIGNATIONS AND |
| COORDINATED ANY CHANGES AS NEEDED. |
| |
| |
| 3) NOTE: PLEASE KNOW AT THIS TIME THERE ARE NO COMMENTS |
| ON SHEETS 2.1,2.2,4.1,5.1 AND 6.1 HOWEVER BASED ON |
| OTHER COMMENTSTHESE MAY OR MAY NOT BE REVISED. |
| IF NO REVISIONS ARE MADE PLEASE BE SURE TO SUBMIT THESE |
| SHEETS BACK WHEN OTHER CORRECTIONS. |
| |
| |
| |
| |
| **IMPORTANT** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPARTMENT |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |