Plan Review Notes For Permit 07090764 |
Permit Number |
07090764 |
|
Review Stop |
M |
Sequence Number |
7 |
|
Notes |
Date |
Text |
2008-07-03 16:25:07 | REVIEW #: REVISION 4 | | ACTION: DENIED | | | | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | 1. DATA CLOSET 2.201A IS BEING CONVERTED INTO A RETURN | | AIRR PLENUM BY INSTALLING THE AHU FOR THE | | CONFERENCE/TRAINING ROOM IN THERE. PROVIDE | | DOCUMENTATION SHOWING ALL DATA EQUIPMENT AND ALL | | ASSOCIATED MATERIALS EXPOSED WITHIN THIS PLENUM TO BE | | NONCOMBUSTIBLE OR HAS A FLAME SPREAD INDEX OF NOT MORE | | THAN 25 AND A SMOKE-DEVELOPED INDEX OF NOT MORE THAN 50 | | WHEN TESTED IN ACCORDANCE WITH ASTM E84 PER FBCM | | 606.2.1. | | | | 2. THE DOOR ON DATA CLOSET 2.201A IS SHOWN ON DOOR | | SCHEDULE TO BE MADE OF WOOD. THIS DOOR MUST ALSO BE IN | | COMPLIANCE WITH FBCM 606.2.1. | | | | 3. IS CLOSET 2.204A ALSO TO BE A PLENUM? IF SO, THIS | | DOOR IS ALSO SHOWN ON DOOR SCHEDULE TO BE WOOD. THIS | | DOOR MUST BE IN COMPLIANCE WITH FBCM 606.2.1. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J. REGUEIRO | | 561.805.6719 | | [email protected] |
|