Plan Review Notes
Plan Review Notes For Permit 07090764
Permit Number 07090764
Review Stop P
Sequence Number 6
Notes
Date Text
2008-06-26 12:39:23REVISION DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHT P1.1 REVISIONS ARE REQUIRED FOR THE STORM &
 CONDENSATE RISER DIAGRAMS TO REFLECT CHANGES TO THESE
 SYSTEMS. PLEASE INDICATE HOW THE CONDENSATE CONNECTS TO
 THE STORM AT COL LINE 2.1/H-J AND COL LINE 3-2.1/C-D.
 REVISIONS FOR RISER DIAGRAMS SHALL BE SUBMITTED WHEN
 SHT P1.1 SO CONNECTIONS CAN BE APPROVED WITH FLOOR PLAN
 CHANGES. SECTIONS 106.1.1, 106.1.3, 106.3.5.1.3 314.2.1
 &1101.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  