Plan Review Notes
Plan Review Notes For Permit 07090764
Permit Number 07090764
Review Stop E
Sequence Number 6
Notes
Date Text
2008-06-25 11:54:59** DENIEDREVIEW **
  
  
  
 1)NOTE: PLEASESEE SHEET E1.1 WHICH STATES REVISIONS
 DUE TO PERMIT COMMENTS HOWEVERTHERE IS NO RECORD OF
 ANY COMMENTS.
 PLEASE COORDINATE PLANS OR PROVIDE A RESPONSE FOR
 REVISED ITEMS TO CLARIFY.
 106.5, 106.1.1
  
 2) NOTE: PLEASE SEE THE STORAGE ROOM WHICH HAS NOW BEEN
 CHANGED TO THE *METER STORAGE* HOWEVER IS ALSO NOW A
 WORK SHOP OF SORTS.
 THIS ROOM HAS NOW BEEN AIR CONDITIONED WHICH WILL
 REQUIRE THE ENERGY CALCULATIONS TO BE REVISED. PLEASE
 SEE SHEET 3.1 WHICH DOES NOT HAVE THE REVISED ROOM
 LAYOUT.
 PLEASE COORDINATE PLANS.
 FBC 106.5,106.1.1,106.1.2
 FBC CHAPTER 13, 13-400.3.B.
  
 3) NOTE: PLEASE SEE SHEET E3.1 WHICH STATES A REVISION
 #5. THE ONLY REV #5 ON SHEET WAS UNDER ONE OF THE SCALE
 DETAILS. THIS SCALE DETAIL SHOWING 1/4INCH = 1FTIS
 THE SAME AS PREVIOUS PLANS WHICH INDICATED A REV #4
 WITH THE SAME LOCATION CONTAINING A CLOUD FOR REVISING
 THE SCALE.
 A REVISED PLAN ALONG WITH CLOUDS OR TRIANGLES SHOWING
 THE REVISED ITEMS NEEDS TO BE SUBMITTED. PLEASE KNOW
 ANY REVISIONS MAY ALSO BE NOTED IN A LETTER INFORMING
 THE REVIEWER OF CHANGE. THE LETTER IS NOT REQUIRED
 HOWEVER IS HELPFUL IN THE REVIEW PROCESS.
 FBC 106.1.1, 106.1.2, 106.5 FOR COORDINATION AND
 CLARITY OF RECORD PLANS.
  
 4) NOTE: THE RISER HAS BEEN REVISED AND COORDINATE WITH
 PANEL SCHEDULES ETC ARE NEEDED.
 PLEASE SEE 1EGH SHOWS THIS PANEL FED FROM EDP HOWEVER
 EDP NO LONGER EXISTS.
 PLEASE SEE SDP SHOWS BEING FED FROM EM ATS HOVER BASED
 ON THE RISER THIS IS NO LONGER FED FROM THE EM ATS.
 408.4
 FBC 106.1.1, 106.1.2, 106.5 FOR COORDINATION AND
 CLARITY OF REVISED PLANS.
  
 5) NOTE: PLEASE SE THE MGP SHOWS SOME SORT OF
 DISCONNECTING MEANS ON RISER FOR FEEDERS FROM THE
 GENERATOR. BASED ON THE MGP PANEL SCHEDULE THIS IS A
 MAIN LUG ONLY PANEL.
 AS SHOWN ALL BREAKERS ON LOAD SIDE OF THE GENERATOR
 BREAKERS ARE NOW DISCONNECTS FOR THE GENERATOR
 FEEDERS.
  
 PLEASE BE SURE TO CLARIFY THE DISCONNECT SHOWN ON THE
 RISER CIRCLED IN RED ON ONE SET.
 PLEASE LABEL WITH NOTES FOR SIGNAGE THAT THE BREAKERS
 ON THE GENERATOR ARE NOW THE NEW DISCONNECTS FOR THE
 EMERGENCY POWER. THIS IS BASED ON THE RISER AS SHOWN.
 IF EQUIPMENT CHANGES OR THERE IS ACTUALLY A DISCONNECT
 WHICH IS NOT LABELED, THEN THIS COMMENT MAY CHANGE.
 PLEASE CALL TO GO OVER COMMENT.
 PLEASE VERIFY IF THE MGP MEETS SWITCHBOARD OR PANEL
 BOARD. PLEASE SEE COMMENTARY OF 700.9B BELOW.
 FBC 106.1.1, 106.1.2 FOR CLARITY AND COORDINATION. NEC
 230.2E, 700.9B (FOR MGP) , 700.8, 701.9, 702.8
  
 6) NOTE: PLEASE KNOW AS REDLINED ON ORIGINAL PLANS: NO
 LOW VOLTAGE PERMITS HAVE BEEN APPLIED FOR OR ISSUED FOR
 THE LOW VOLTAGE SYSTEMS SHOWN ON PLANS.
 THIS IS GIVEN FOR INFORMATION SO PERMIT CAN BE APPLIED
 FOR BEFORE SCOPE OF WORK COMMENCES.
  
 7) NOTE: PLEASE VERIFY WHY PHOTO-METRICS FOR ENTIRE
 BUILDIGN ARE BEING SUBMITTED. IF LIGHTING PLANS ARE NOT
 BEING REVISED FORAREAS AS SHOWN THEN REVISED
 PHOTO-METRICS ARE NOT NEEDED.
  
  
 **WHERE AN ALTERNATE POWER SOURCE SUPPLIES A
 SWITCHBOARD FROM A SINGLE FEEDER OR FEEDERS IN
 PARALLEL, THAT SWITCHBOARD MAY FURTHER DISTRIBUTE AND
 PROVIDE POWER FOR THE EMERGENCY, LEGALLY REQUIRED, AND
 OPTIONAL STANDBY SYSTEMS.
 SWITCHBOARDS PROVIDE THE PHYSICAL SEPARATION
 REQUIREMENTS OF BOTH SYSTEM AND WIRING FROM A COMMON
 POWER SOURCE. THIS PHYSICAL SEPARATION CANNOT OCCUR
 WITHIN A PANELBOARD ENCLOSURE BECAUSE OF ITS OPEN
 DESIGN. INDIVIDUAL OVERCURRENT SECTIONS CAN SUPPLY
 EMERGENCY, LEGALLY REQUIRED, AND OPTIONAL STANDBY
 TRANSFER SWITCHES.**
  
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]