2008-06-25 11:54:59 | ** DENIEDREVIEW ** |
| |
| |
| |
| 1)NOTE: PLEASESEE SHEET E1.1 WHICH STATES REVISIONS |
| DUE TO PERMIT COMMENTS HOWEVERTHERE IS NO RECORD OF |
| ANY COMMENTS. |
| PLEASE COORDINATE PLANS OR PROVIDE A RESPONSE FOR |
| REVISED ITEMS TO CLARIFY. |
| 106.5, 106.1.1 |
| |
| 2) NOTE: PLEASE SEE THE STORAGE ROOM WHICH HAS NOW BEEN |
| CHANGED TO THE *METER STORAGE* HOWEVER IS ALSO NOW A |
| WORK SHOP OF SORTS. |
| THIS ROOM HAS NOW BEEN AIR CONDITIONED WHICH WILL |
| REQUIRE THE ENERGY CALCULATIONS TO BE REVISED. PLEASE |
| SEE SHEET 3.1 WHICH DOES NOT HAVE THE REVISED ROOM |
| LAYOUT. |
| PLEASE COORDINATE PLANS. |
| FBC 106.5,106.1.1,106.1.2 |
| FBC CHAPTER 13, 13-400.3.B. |
| |
| 3) NOTE: PLEASE SEE SHEET E3.1 WHICH STATES A REVISION |
| #5. THE ONLY REV #5 ON SHEET WAS UNDER ONE OF THE SCALE |
| DETAILS. THIS SCALE DETAIL SHOWING 1/4INCH = 1FTIS |
| THE SAME AS PREVIOUS PLANS WHICH INDICATED A REV #4 |
| WITH THE SAME LOCATION CONTAINING A CLOUD FOR REVISING |
| THE SCALE. |
| A REVISED PLAN ALONG WITH CLOUDS OR TRIANGLES SHOWING |
| THE REVISED ITEMS NEEDS TO BE SUBMITTED. PLEASE KNOW |
| ANY REVISIONS MAY ALSO BE NOTED IN A LETTER INFORMING |
| THE REVIEWER OF CHANGE. THE LETTER IS NOT REQUIRED |
| HOWEVER IS HELPFUL IN THE REVIEW PROCESS. |
| FBC 106.1.1, 106.1.2, 106.5 FOR COORDINATION AND |
| CLARITY OF RECORD PLANS. |
| |
| 4) NOTE: THE RISER HAS BEEN REVISED AND COORDINATE WITH |
| PANEL SCHEDULES ETC ARE NEEDED. |
| PLEASE SEE 1EGH SHOWS THIS PANEL FED FROM EDP HOWEVER |
| EDP NO LONGER EXISTS. |
| PLEASE SEE SDP SHOWS BEING FED FROM EM ATS HOVER BASED |
| ON THE RISER THIS IS NO LONGER FED FROM THE EM ATS. |
| 408.4 |
| FBC 106.1.1, 106.1.2, 106.5 FOR COORDINATION AND |
| CLARITY OF REVISED PLANS. |
| |
| 5) NOTE: PLEASE SE THE MGP SHOWS SOME SORT OF |
| DISCONNECTING MEANS ON RISER FOR FEEDERS FROM THE |
| GENERATOR. BASED ON THE MGP PANEL SCHEDULE THIS IS A |
| MAIN LUG ONLY PANEL. |
| AS SHOWN ALL BREAKERS ON LOAD SIDE OF THE GENERATOR |
| BREAKERS ARE NOW DISCONNECTS FOR THE GENERATOR |
| FEEDERS. |
| |
| PLEASE BE SURE TO CLARIFY THE DISCONNECT SHOWN ON THE |
| RISER CIRCLED IN RED ON ONE SET. |
| PLEASE LABEL WITH NOTES FOR SIGNAGE THAT THE BREAKERS |
| ON THE GENERATOR ARE NOW THE NEW DISCONNECTS FOR THE |
| EMERGENCY POWER. THIS IS BASED ON THE RISER AS SHOWN. |
| IF EQUIPMENT CHANGES OR THERE IS ACTUALLY A DISCONNECT |
| WHICH IS NOT LABELED, THEN THIS COMMENT MAY CHANGE. |
| PLEASE CALL TO GO OVER COMMENT. |
| PLEASE VERIFY IF THE MGP MEETS SWITCHBOARD OR PANEL |
| BOARD. PLEASE SEE COMMENTARY OF 700.9B BELOW. |
| FBC 106.1.1, 106.1.2 FOR CLARITY AND COORDINATION. NEC |
| 230.2E, 700.9B (FOR MGP) , 700.8, 701.9, 702.8 |
| |
| 6) NOTE: PLEASE KNOW AS REDLINED ON ORIGINAL PLANS: NO |
| LOW VOLTAGE PERMITS HAVE BEEN APPLIED FOR OR ISSUED FOR |
| THE LOW VOLTAGE SYSTEMS SHOWN ON PLANS. |
| THIS IS GIVEN FOR INFORMATION SO PERMIT CAN BE APPLIED |
| FOR BEFORE SCOPE OF WORK COMMENCES. |
| |
| 7) NOTE: PLEASE VERIFY WHY PHOTO-METRICS FOR ENTIRE |
| BUILDIGN ARE BEING SUBMITTED. IF LIGHTING PLANS ARE NOT |
| BEING REVISED FORAREAS AS SHOWN THEN REVISED |
| PHOTO-METRICS ARE NOT NEEDED. |
| |
| |
| **WHERE AN ALTERNATE POWER SOURCE SUPPLIES A |
| SWITCHBOARD FROM A SINGLE FEEDER OR FEEDERS IN |
| PARALLEL, THAT SWITCHBOARD MAY FURTHER DISTRIBUTE AND |
| PROVIDE POWER FOR THE EMERGENCY, LEGALLY REQUIRED, AND |
| OPTIONAL STANDBY SYSTEMS. |
| SWITCHBOARDS PROVIDE THE PHYSICAL SEPARATION |
| REQUIREMENTS OF BOTH SYSTEM AND WIRING FROM A COMMON |
| POWER SOURCE. THIS PHYSICAL SEPARATION CANNOT OCCUR |
| WITHIN A PANELBOARD ENCLOSURE BECAUSE OF ITS OPEN |
| DESIGN. INDIVIDUAL OVERCURRENT SECTIONS CAN SUPPLY |
| EMERGENCY, LEGALLY REQUIRED, AND OPTIONAL STANDBY |
| TRANSFER SWITCHES.** |
| |
| |
| ** IMPORTANT** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |