2008-04-03 18:47:35 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBCFLORIDA BUILDING CODE 2004 |
| FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| CODE |
| FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL |
| FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| FAC FLORIDA ADMINISTRATIVE CODE |
| FSFLORIDA STATUTE |
| |
| 1.SEE ELECTRICAL AND MECHANICAL COMMENTS REGARDING |
| ENERGY CALCS.CODE COMPLIANT ENERGY CALCS ARE REQUIRED |
| PRIOR TO PERMIT ISSUANCE AND CANNOT BE PROVISO'D AS |
| FLORIDA STATUTORY ITEMS CANNOT BE PROVISO ITEMS. |
| |
| 2.SEE THE SUBMITTED ENERGY CALCS.NO DOORS ARE |
| SHOWN.TWO WINDOWS ARE SHOWN, BUT THE PLAN SHOWS MORE |
| THAN TWO WINDOWS.THE DESCRIPTION STATES THAT THE |
| DESCRIPTION IS "CLEMATIS GARAGE - ELECTRIC" BUT THE |
| ENERGY CALC NEEDS TO SHOW ALL BUILDING COMPONENTS AS |
| REQUIRED. |
| |
| 3.OWNER/AGENT IS TO SIGN THE ENERGY CALCS PRIOR TO |
| SUBMITTAL, FBC13-103.1. |
| |
| 4.SEE ENERGY CALC PAGE WITH "OTHER REQUIRED |
| COMPLIANCE" TITLE, SHEET 7.PLEASE COMPLETE. |
| |
| 5.NOTHING IS SHOWN IN THE COMPONENT "FLOORS", PAGE 5 |
| OF THE ENERGY CALC, BUT CONFERENCE ROOM AND OFFICES |
| HAVE A FLOOR OVER UNCONDITIONED SPACE. |
| |
| 6.THIS IS NOT AN EXHAUSTIVE LIST AS ENERGY CALCS ARE |
| SPOT CHECKED FOR COMPLIANCE.PLEASE CHECK ALL |
| COMPONENTS AND CONFIRM THAT INSULATION ON THE ENERGY |
| CALC MATCHES INSULATION ON THE PLAN. |
| |
| PURSUANT TO CONTRACTOR'S REQUEST, THE PERMIT WILL BE |
| ISSUED WITH THE FOLLOWING PROVISOS: |
| |
| 1.PROVIDE PRECAST FASTENING (ITEM 23B) |
| |
| 2.PROVIDE METHOD OF ATTACHMENT PRECAST PILASTER (ITEM |
| 26) |
| |
| 3.APPLY FOR LOCAL PRODUCT APPROVAL, INGERSOLL RAND |
| REPORT S07-001 (29A) |
| |
| 4.REVISE FIRE RESISTIVE DESIGN SHEETS (LS1-D1 THROUGH |
| 3) TO INCLUDE UL U905 AND UL U926. |
| |
| 5.REVISE DETAIL C4 A5-D.1 TO INCLUDE UL ASSEMBLY OR |
| CALCULATED FIRE RESISTANCE. |
| |
| 6.SUBMIT PRODUCT APPROVAL FOR DOORS IN ZONE 5. |
| |